الوصف
Product Description
The KL3101X1-BA1 is an intrinsically safe (I.S.) analog input CHARM module from Emerson, engineered for DeltaV systems. It allows safe acquisition of 4–20 mA signals from HART-enabled field devices in hazardous environments, providing both measurement and diagnostic capabilities in a compact CHARM form factor.
This module is designed for installations in Zone 2 / Class I Division 2 areas, combining intrinsic safety, robust environmental tolerance, and compliance with ATEX, IECEx, FM, and UKEX standards. Its low-power CHARM bus interface and reliable 24 VDC field circuit support stable operation under demanding conditions.
Core Technical Specifications
-
Model: KL3101X1-BA1
-
Module Type: Intrinsically Safe Analog Input (I.S.) CHARM
-
Signal Type: 4–20 mA analog input with HART communication
-
Safety Classification: Intrinsically Safe (I.S.)
-
CHARM Bus Power: +6.3 VDC, 0 A nominal
-
Field Circuit Power: +24 VDC at 60 mA
-
Terminal Block Key: A1
-
Operating Temperature: –40 °C to +70 °C
-
Relative Humidity: 5–95%, non-condensing
-
Shock Resistance: 10 g, half-sine, 11 ms
-
Vibration: 2–13.2 Hz: 1 mm peak-to-peak; 13.2–150 Hz: 0.7 g
-
Airborne Contaminants Rating: ISA-S71.04 Class G3
-
Weight: 0.14 lbs
Safety & Compliance
-
Hazardous Atmosphere Ratings:
-
II 3(1) G Ex ec [ia Ga] IIC Gc
-
II 3G (1D) Ex ec [ia IIIC Da] IIC Gc
-
Class I, Division 2, Groups A–D
-
Zone 2 AEx ec [ia Ga / IIIC Da]
-
Certifications: ATEX, IECEx, FM, UKEX
-
Installation Note: Must not be inserted or removed while energized unless the area is confirmed non-hazardous
Functional Advantages
-
Intrinsically safe design suitable for hazardous locations
-
HART support enables device diagnostics and configuration without extra wiring
-
Wide environmental tolerance for extreme temperatures and airborne contaminants
-
Compact CHARM format integrates seamlessly into DeltaV I/O systems
-
Maintenance-free operation; no calibration required
Applications
-
Oil and gas process control panels
-
Chemical and petrochemical plant field monitoring
-
Remote hazardous area I/O installations
-
Integration with DeltaV distributed control systems
FAQ
Q: Can this module operate in Zone 2 / Class I Div. 2 hazardous areas?
A: Yes, the KL3101X1-BA1 is certified intrinsically safe for Zone 2 / Class I Division 2 locations.
Q: Does it require periodic calibration?
A: No, the module is maintenance-free and factory-calibrated.
Q: What HART capabilities does it support?
A: Full pass-through communication for diagnostics and configuration of HART-enabled transmitters.
الميزات
نحن نرحب بالطلبات الكبيرة ولدينا حد أدنى للطلب يبلغ وحدة واحدة فقط.
عند الطلب، يمكننا توفير جميع الوثائق اللازمة، بما في ذلك شهادات المنشأ/المطابقة وغيرها من مستندات التصدير المطلوبة.
بالنسبة للعناصر المتوفرة في المخزون، نهدف إلى التسليم خلال 1-3 أيام بعد تأكيد الدفع. سيتم تسليم العناصر التي لها أوقات انتظار محددة وفقًا للجدول المقتبس.
نحن نقبل الدفع بنسبة 100% عن طريق التحويل البرقي (T/T) قبل الشحن. بالنسبة للعناصر التي لها أوقات انتظار، يتطلب دفع 30% كدفعة مقدمة، مع دفع الـ 70% المتبقية قبل الشحن. بالنسبة لتحويلات اليوان الصيني (RMB)، يرجى الاتصال بنا إذا كان لديك وكيل في الصين.
نحن نقدم ضمانًا قياسيًا لمدة سنة واحدة على جميع العناصر الجديدة والأصلية. إذا كنت بحاجة إلى ضمان ممتد، يرجى الاتصال بنا للحصول على تفاصيل التكلفة الإضافية.
رضاكم مهم بالنسبة لنا. إذا كنت بحاجة إلى إرجاع عنصر، يجب أن يتم ذلك خلال 30 يومًا من تاريخ الطلب. يجب أن يكون المنتج غير مستخدم، غير مفتوح، وفي عبوته الأصلية مع جميع الملحقات المرفقة. تتم معالجة المبالغ المستردة خلال 5-7 أيام عمل بعد استلامنا للعنصر المُعاد. يرجى ملاحظة أن رسوم الشحن والرسوم ذات الصلة غير قابلة للاسترداد.