Descripción
Product Description
The KL3103X1-BA1 is an intrinsically safe (I.S.) digital input CHARM module from Emerson, designed for DeltaV systems. It supports 24 VDC dry contact signals, allowing direct connection of field devices such as switches, pushbuttons, and contact closures. This module ensures safe and reliable monitoring in hazardous locations, integrating seamlessly into the DeltaV CHARM architecture.
Engineered for Zone 2 / Class I Division 2 environments, the KL3103X1-BA1 combines intrinsic safety with robust environmental tolerance, including resistance to vibration, shock, and airborne contaminants. Its compact form factor and low-power CHARM bus interface facilitate easy installation and modular expansion.
Core Technical Specifications
-
Model: KL3103X1-BA1
-
Module Type: Intrinsically Safe Digital Input (DI) CHARM
-
Signal Type: 24 VDC dry contact
-
Safety Classification: Intrinsically Safe (I.S.)
-
CHARM Bus Power: +6.3 VDC, 32 mA
-
Field Circuit Power: +24 VDC, ~10 mA
-
Channels: Single-channel input
-
Terminal Block Key: 2C
-
Operating Temperature: –40 °C to +70 °C
-
Relative Humidity: 5–95% RH, non-condensing
-
Shock Resistance: 10 g, half-sine wave, 11 ms
-
Vibration: 2–13.2 Hz: 1 mm peak-to-peak; 13.2–150 Hz: 0.7 g
-
Airborne Contaminants Rating: ISA-S71.04 Class G3
-
Weight: 0.18 lbs
Safety & Compliance
-
Hazardous Area Ratings:
-
II 3G Ex nA [nL] IIC Gc
-
II 3G Ex ec [ic] IIC Gc
-
Class I, Division 2, Groups A–D
-
Zone 2 AEx/Ex ec [ic] IIC Gc
-
Certifications: ATEX, IECEx, FM, UKEX
-
Installation Note: Module must not be inserted or removed while energized unless the area is confirmed safe
Functional Advantages
-
Intrinsically safe design suitable for hazardous areas
-
Supports 24 VDC dry contact inputs for direct field device monitoring
-
Compact CHARM format allows easy integration and modular expansion
-
Robust diagnostics ensure reliable operation of connected field devices
-
Wide environmental tolerance for harsh industrial conditions
Applications
-
Monitoring switches and pushbuttons in oil and gas facilities
-
Remote hazardous area I/O panels
-
Chemical and petrochemical process control systems
-
DeltaV system integration for single-channel dry contact inputs
FAQ
Q: Is this module suitable for hazardous Zone 2 locations?
A: Yes, the KL3103X1-BA1 is certified intrinsically safe for Zone 2 / Class I Div. 2 hazardous areas.
Q: Can it monitor multiple devices?
A: This module provides a single-channel input; multiple modules can be installed for multi-device monitoring.
Q: Does it require calibration?
A: No calibration is required, and the module has no user-serviceable parts.
Características
Damos la bienvenida a pedidos al por mayor y tenemos una cantidad mínima de pedido de solo una unidad.
Si lo solicita, podemos proporcionar toda la documentación necesaria, incluidos los Certificados de Origen/Conformidad y otros documentos de exportación requeridos.
Para los artículos en stock, nuestro objetivo es entregar dentro de 1-3 días después de la confirmación del pago. Los artículos con plazos especificados se entregarán según el calendario indicado.
Aceptamos pago 100% T/T (Transferencia telegráfica) antes del envío. Para artículos con tiempos de entrega, se requiere un depósito del 30% por adelantado, con el 70% restante debido antes del envío. Para transferencias en RMB, por favor contáctenos si tiene un agente en China.
Ofrecemos una garantía estándar de un año en todos los artículos nuevos y originales. Si necesita una garantía extendida, por favor contáctenos para obtener detalles sobre costos adicionales.
Su satisfacción es importante para nosotros. Si necesita devolver un artículo, debe hacerlo dentro de los 30 días posteriores a la fecha del pedido. El producto debe estar sin usar, sin abrir y en su embalaje original con todos los accesorios incluidos. Los reembolsos se procesan dentro de 5-7 días hábiles después de que recibamos el artículo devuelto. Tenga en cuenta que los gastos de envío y cargos relacionados no son reembolsables.