Lewati ke konten
Yokogawa NFAR181-S50 Temperature Input Module

Yokogawa NFAR181-S50 Temperature Input Module

  • 1000 Tersedia
  • Manufacturer: Yokogawa

  • Product No.: NFAR181-S50

  • Condition: Tersedia

  • Product Type: Temperature Input Module

  • Product Origin: Japan

  • Payment:T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":42884313972826,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"NFAR181-S50","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Yokogawa NFAR181-S50 Temperature Input Module","public_title":null,"options":["Default Title"],"price":26400,"weight":300,"compare_at_price":37800,"inventory_management":"shopify","barcode":"Japan","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Deskripsi

Overview

The NFAR181-S50 is a multi-channel temperature measurement input module developed by Yokogawa for use in ProSafe-RS safety-instrumented systems and high-reliability control platforms. It is designed to acquire precise temperature data from RTD and thermocouple sensors while maintaining strict electrical isolation between channels, ensuring dependable operation in electrically noisy and safety-critical environments.

This module is commonly deployed in continuous-process industries where temperature integrity directly impacts process safety, equipment protection, and regulatory compliance.

Functional Characteristics

The NFAR181-S50 provides twelve individually isolated input channels, allowing simultaneous measurement of multiple temperature points without signal interference. Each channel supports configurable sensor types, enabling flexible field wiring and simplified spare-parts management across mixed RTD and thermocouple installations.

Integrated cold-junction compensation and digital linearization ensure stable and repeatable measurements across wide temperature ranges. The module is optimized for fast data refresh, supporting control and safety logic that requires timely temperature feedback.

Supported Sensor Inputs

RTD Measurement

  • Pt100 RTD, 3-wire configuration

  • JPt100 RTD, 3-wire configuration

  • Measurement range from −200 °C to +800 °C

  • Typical accuracy up to ±0.15 °C

  • Internal lead-wire resistance compensation

Thermocouple Measurement

  • Compatible thermocouple types include J, K, E, T, B, R, and S

  • Supports additional MIL-standard thermocouple variants

  • Built-in cold-junction compensation

  • Automatic linearization per selected thermocouple type

Performance Specifications

  • Input channels: 12, fully isolated

  • Channel-to-channel isolation: Supported

  • Channel-to-system isolation: Supported

  • Data update interval: Approximately 1 second

  • Long-term measurement stability optimized for continuous operation

  • High resistance to electromagnetic and conducted noise

Mechanical and Environmental Data

  • Module form factor: Compact I/O card for Yokogawa safety systems

  • Dimensions: 130 × 107.5 × 32.8 mm

  • Weight: 0.3 kg

  • Designed for control room and field-mounted safety cabinets

System Compatibility

The NFAR181-S50 is designed for seamless integration with Yokogawa ProSafe-RS safety controllers and related I/O subsystems. Configuration and diagnostics are performed through Yokogawa engineering tools, allowing sensor selection, range assignment, and fault monitoring at the system level.

Typical Applications

  • Safety-instrumented temperature monitoring

  • Burner and furnace protection systems

  • Reactor and vessel temperature supervision

  • Turbine and auxiliary equipment monitoring

  • High-integrity shutdown and alarm systems

Frequently Asked Questions

Can RTD and thermocouple sensors be mixed on the same module?
Yes. Each channel can be configured independently, allowing RTD and thermocouple inputs to coexist on a single NFAR181-S50 module.

Is the module suitable for SIL-rated systems?
Yes. The module is intended for use in Yokogawa ProSafe-RS safety systems and meets the reliability requirements typical of SIL-based architectures when used in approved configurations.

Does the module require external cold-junction compensation hardware?
No. Cold-junction compensation is integrated into the module for thermocouple measurements.

Fitur

Kami menerima pesanan dalam jumlah besar dan memiliki jumlah pesanan minimum hanya satu unit.

Atas permintaan, kami dapat menyediakan semua dokumentasi yang diperlukan, termasuk Sertifikat Asal/Kesesuaian dan dokumen ekspor lain yang dibutuhkan.

Untuk barang yang tersedia, kami berusaha mengirim dalam 1-3 hari setelah konfirmasi pembayaran. Barang dengan waktu tunggu yang ditentukan akan dikirim sesuai jadwal yang telah disebutkan.

Kami menerima pembayaran 100% T/T (Telegraphic Transfer) sebelum pengiriman. Untuk barang dengan waktu tunggu, diperlukan deposit 30% di muka, dengan sisa 70% harus dibayar sebelum pengiriman. Untuk transfer RMB, silakan hubungi kami jika Anda memiliki agen di China.

Kami menawarkan garansi standar satu tahun untuk semua barang baru dan asli. Jika Anda memerlukan garansi tambahan, silakan hubungi kami untuk detail biaya tambahan.

Kepuasan Anda penting bagi kami. Jika Anda perlu mengembalikan barang, itu harus dilakukan dalam waktu 30 hari sejak tanggal pemesanan. Produk harus belum digunakan, belum dibuka, dan dalam kemasan aslinya dengan semua aksesori yang disertakan. Pengembalian dana diproses dalam waktu 5-7 hari kerja setelah kami menerima barang yang dikembalikan. Harap dicatat bahwa biaya pengiriman dan biaya terkait tidak dapat dikembalikan.

Unggulan

Produk pelengkap