Descrizione
Product Description
The KL3101X1-BA1 is an intrinsically safe (I.S.) analog input CHARM module from Emerson, engineered for DeltaV systems. It allows safe acquisition of 4–20 mA signals from HART-enabled field devices in hazardous environments, providing both measurement and diagnostic capabilities in a compact CHARM form factor.
This module is designed for installations in Zone 2 / Class I Division 2 areas, combining intrinsic safety, robust environmental tolerance, and compliance with ATEX, IECEx, FM, and UKEX standards. Its low-power CHARM bus interface and reliable 24 VDC field circuit support stable operation under demanding conditions.
Core Technical Specifications
-
Model: KL3101X1-BA1
-
Module Type: Intrinsically Safe Analog Input (I.S.) CHARM
-
Signal Type: 4–20 mA analog input with HART communication
-
Safety Classification: Intrinsically Safe (I.S.)
-
CHARM Bus Power: +6.3 VDC, 0 A nominal
-
Field Circuit Power: +24 VDC at 60 mA
-
Terminal Block Key: A1
-
Operating Temperature: –40 °C to +70 °C
-
Relative Humidity: 5–95%, non-condensing
-
Shock Resistance: 10 g, half-sine, 11 ms
-
Vibration: 2–13.2 Hz: 1 mm peak-to-peak; 13.2–150 Hz: 0.7 g
-
Airborne Contaminants Rating: ISA-S71.04 Class G3
-
Weight: 0.14 lbs
Safety & Compliance
-
Hazardous Atmosphere Ratings:
-
II 3(1) G Ex ec [ia Ga] IIC Gc
-
II 3G (1D) Ex ec [ia IIIC Da] IIC Gc
-
Class I, Division 2, Groups A–D
-
Zone 2 AEx ec [ia Ga / IIIC Da]
-
Certifications: ATEX, IECEx, FM, UKEX
-
Installation Note: Must not be inserted or removed while energized unless the area is confirmed non-hazardous
Functional Advantages
-
Intrinsically safe design suitable for hazardous locations
-
HART support enables device diagnostics and configuration without extra wiring
-
Wide environmental tolerance for extreme temperatures and airborne contaminants
-
Compact CHARM format integrates seamlessly into DeltaV I/O systems
-
Maintenance-free operation; no calibration required
Applications
-
Oil and gas process control panels
-
Chemical and petrochemical plant field monitoring
-
Remote hazardous area I/O installations
-
Integration with DeltaV distributed control systems
FAQ
Q: Can this module operate in Zone 2 / Class I Div. 2 hazardous areas?
A: Yes, the KL3101X1-BA1 is certified intrinsically safe for Zone 2 / Class I Division 2 locations.
Q: Does it require periodic calibration?
A: No, the module is maintenance-free and factory-calibrated.
Q: What HART capabilities does it support?
A: Full pass-through communication for diagnostics and configuration of HART-enabled transmitters.
Caratteristiche
Accogliamo ordini all'ingrosso e abbiamo una quantità minima d'ordine di una sola unità.
Su richiesta, possiamo fornire tutta la documentazione necessaria, inclusi i Certificati di Origine/Conformità e altri documenti di esportazione richiesti.
Per gli articoli in magazzino, puntiamo a consegnare entro 1-3 giorni dalla conferma del pagamento. Gli articoli con tempi di consegna specificati saranno consegnati secondo il programma indicato.
Accettiamo il pagamento 100% T/T (Trasferimento Telegrafico) prima della spedizione. Per gli articoli con tempi di consegna, è richiesto un deposito del 30% anticipato, con il restante 70% da pagare prima della spedizione. Per i trasferimenti in RMB, si prega di contattarci se avete un agente in Cina.
Offriamo una garanzia standard di un anno su tutti gli articoli nuovi e originali. Se desideri una garanzia estesa, contattaci per i dettagli sui costi aggiuntivi.
La tua soddisfazione è importante per noi. Se devi restituire un articolo, deve essere fatto entro 30 giorni dalla data dell'ordine. Il prodotto deve essere inutilizzato, non aperto e nella sua confezione originale con tutti gli accessori inclusi. I rimborsi vengono elaborati entro 5-7 giorni lavorativi dopo aver ricevuto l'articolo restituito. Si prega di notare che le spese di spedizione e i costi correlati non sono rimborsabili.