{"product_id":"yokogawa-aap135-s50-13s00-pulse-input-module","title":"Yokogawa AAP135-S50\/13S00 Pulse Input Module","description":"\u003ch3\u003eOverview\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eAAP135-S50\/13S00\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eis an 8-channel pulse input module. It works with Yokogawa’s CENTUM CS 3000 and ProSafe-RS distributed control systems. The module accepts contact ON\/OFF signals, voltage pulses, and current pulses. It suits flow measurement, pulse counting, and event detection tasks. Each channel provides electrical isolation, ensuring reliable performance and noise immunity in industrial settings.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eModel:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eAAP135-S50\/13S00\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eInput Channels:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e8 (isolated)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eInput Signal Types:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eContact ON\/OFF, voltage pulse, current pulse\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eInput Frequency Range:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e0 to 10 kHz\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eMinimum Pulse Width:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e40 µs\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eVoltage Levels:\u003c\/strong\u003e\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eHigh (VH): 3–24 V DC\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eLow (VL): 1–8 V DC\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eSwing (VH–VL): ≥ 3 V\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eContact Input Resistance:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eOpen ≥ 100 kΩ, Closed ≤ 200 Ω\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eWithstand Voltage:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e500 V AC for 1 minute between inputs and system, and between channels\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003ePower Supply:\u003c\/strong\u003e\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e5 V DC, max 300 mA\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e24 V DC, max 400 mA\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eTransmitter Power Supply:\u003c\/strong\u003e\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e12 V DC ±10%, max 40 mA\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e24 V DC ±10%, max 30 mA\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eSignal Filtering:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eConfigurable anti-chatter filter\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eData Update Cycle:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e2 ms\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eMounting:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eDIN rail or panel mount\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eConnections:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eIsolated screw terminals\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eWeight: \u003c\/strong\u003e0.3 kg\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eOperating Temperature:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e–20°C to +70°C\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eConfiguration:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eSupports dual-redundant setup for higher reliability\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eSuffix Code Explanation for\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eAAP135-S50\/13S00\u003c\/strong\u003e\n\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eS\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e– Standard type\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003e5\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e– No explosion protection\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003e0\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e– Basic type\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003e\/13S00\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e– Equipped with a pressure clamp terminal block for isolated analog signals\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eModel ATI-00\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003e– Specifies the terminal block configuration used\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":42004936884314,"sku":"AAP135-S50\/13S00","price":207.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/AAP135-S5013S00.jpg?v=1750391274","url":"https:\/\/www.plcmasters.com\/lt\/products\/yokogawa-aap135-s50-13s00-pulse-input-module","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}