{"id":43736434835546,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"1784-PKTX","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"1784-PKTX Allen-Bradley Bus Communication Card","public_title":null,"options":["Default Title"],"price":12300,"weight":231,"compare_at_price":32000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Allen-Bradley 1784-PKTX Bus Communication Card

The Allen-Bradley 1784-PKTX, also cataloged as the 1784-PKTX Bus Communication Card, operates as a dedicated hardware component for PCI-based network interface communication within PLC-5 and SLC control system platforms. The card provides physical PCI 2.3 connectivity with Data Highway Plus (DH+), Remote I/O (RIO), and DH-485 communication channels.

Hardware Specifications

Parameter Specification
Model 1784-PKTX
Brand Allen-Bradley
Origin United States
Weight 0.51 lbs
Module Type Bus Communication Card
PCI Interface PCI 2.3 compliant
Communication Protocol Data Highway Plus (DH+), Remote I/O (RIO), DH-485
Communication Channels Channel 1A: DH+/RIO, Channel 1C: DH-485
Maximum Modules per System 4
Compatible Controllers PLC-5, PLC-5/250, SLC 5/04 processors; SLC 5/01, SLC 5/02, SLC 5/03 via 1785-KA5
Remote I/O Scanner Supported
Status Indicators One diagnostic/status LED per channel
Wiring Arm 1771-WN
Coating Conformal Coat
Typical AC Signal Delay (Off) 29 +/- 8 ms
Typical DC Signal Delay (Off) 30 +/- 7 ms
DH+/RIO Cable Distance 10,000 ft (3048 m) at 57.6K bit/s; 5,000 ft (1524 m) at 115.2K bit/s; 2,500 ft (762 m) at 230.4K bit/s
DH-485 Cable Distance 4,000 ft (1219 m) at 1200, 2400, 4800, 9600, or 19,200 bits/s

EtherNet/IP and PLC Communication Bus Characteristics

The 1784-PKTX integrates a PCI 2.3 local bus interface with Allen-Bradley legacy communication networks. The card provides dedicated physical ports for DH+/RIO and DH-485 signal exchange through Phoenix connectors. Communication channel operation is controlled through the host computer PCI interface without requiring external power input.

The card supports Remote I/O scanner functions and provides diagnostic feedback through independent channel status LEDs. The conformal-coated PCB assembly supports installation in industrial computer environments where electrical protection of the communication hardware is required.

The module supports industrial control network integration through PLC-5 and SLC processor communication paths. Firmware and driver compatibility depend on the host computer operating environment and installed Allen-Bradley communication software.

Frequently Asked Questions

Q: Does the 1784-PKTX require an external power supply?
A: No. The module receives operating power through the PCI bus interface and does not require a separate external power connection.

Q: Which communication networks are supported by the 1784-PKTX?
A: The card supports Data Highway Plus (DH+), Remote I/O (RIO), and DH-485 communication through dedicated communication channels.

Q: How many 1784-PKTX modules can be installed in one system?
A: A maximum of four 1784-PKTX modules can be installed per system configuration.

Field Installation Guidelines

Install the 1784-PKTX card into a compatible PCI 2.3 expansion slot and verify that the host computer hardware and communication drivers support the installed configuration.

Connect DH+/RIO and DH-485 field wiring according to the applicable Allen-Bradley network wiring standards. Maintain cable separation from high-voltage power conductors and high-noise sources such as motor drives or switching devices.

Terminate communication cable shields according to system grounding requirements. Use proper grounding methods to reduce electromagnetic interference on communication signals. Verify connector pin assignments before energizing the network interface.

Configure communication parameters within the control software environment and confirm channel diagnostic LED status after installation.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products