Allen-Bradley 1746-NR8/C RTD/Resistance Input Module

Allen-Bradley 1746-NR8/C RTD/Resistance Input Module

  • 16 In stock
  • Manufacturer: Allen-Bradley

  • Product No.: 1746-NR8/C

  • Condition: In stock

  • Product Type: RTD/Resistance Input Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 340g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":43505377968218,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"1746-NR8\/C","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Allen-Bradley 1746-NR8\/C RTD\/Resistance Input Module","public_title":null,"options":["Default Title"],"price":12300,"weight":340,"compare_at_price":32000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Allen-Bradley 1746-NR8/C RTD/Resistance Input Module

Configured for RTD signal acquisition and resistance measurement in SLC 500 I/O backplane systems, the Allen-Bradley 1746-NR8/C (1746-NR8 RTD/Resistance input module) provides direct electrical conversion of low-level temperature resistance signals into backplane digital data. The module operates across an 8-channel input architecture with sigma-delta conversion and internal filtering for sensor-level signal conditioning.

The unit is designed for RTD sensor interfacing including Pt and Ni element types, performing multi-channel temperature acquisition through the SLC 500 chassis communication bus.

Suffix Breakdown & Model Matrix

  • 1746: SLC 500 I/O platform

  • NR8: 8-channel RTD/Resistance input function block

  • C: Revision / series suffix level

Hardware Specifications

Parameter Specification
Model 1746-NR8/C
Brand Allen-Bradley
Weight 0.34 kg
Dimensions 144.5 x 34.6 x 130.18 mm
Operating Temp 0 to 60 deg C
Power Consumption ~1.7 W
Input Channels 8 RTD/Resistance inputs
Supported RTD Types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Cu10
Resolution 16-bit
Conversion Method Sigma-Delta A/D
Backplane Current ~100 mA at 5 V DC, ~55 mA at 24 V DC
Update Rate 100 to 400 ms
Isolation Channel-to-channel isolation

I/O Density Scaling within SLC 500 Backplane Architecture

The module participates in SLC 500 backplane bus timing where input data is mapped cyclically during scan execution. Channel multiplexing is managed internally to maintain deterministic update sequencing across 8 RTD inputs, with backplane bandwidth allocation dependent on chassis slot configuration. Signal conditioning is executed prior to bus transfer to minimize scan-cycle distortion under multi-module loading conditions.

Frequently Asked Questions

Q: Can the module be hot-swapped under energized SLC 500 backplane conditions?
A: Hot-swapping is not supported. Removal or insertion requires chassis power removal due to backplane electrical coupling and signal line referencing.

Q: How does backplane current draw affect multi-slot SLC 500 configurations?
A: Backplane consumption at 5 V DC and 24 V DC must be included in chassis power budget calculations to avoid voltage droop during full-slot population.

Q: Does firmware level impact RTD conversion behavior or scaling?
A: Scaling and conversion behavior is fixed in hardware conversion logic; revision suffix affects compatibility but not measurement algorithm.


Field Installation Guidelines

  • Install module only in SLC 500 compatible chassis slot with verified backplane alignment.

  • Maintain shield continuity for RTD cable pairs and terminate shield at single-point ground reference.

  • Separate RTD wiring from high-voltage or switching conductors to reduce inductive coupling.

  • Verify channel wiring configuration (2-wire, 3-wire, 4-wire) before energizing system.

  • Ensure chassis power is removed prior to insertion or removal of module.

  • Confirm terminal block seating and mechanical locking before system startup.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products