{"product_id":"allen-bradley-1762-iq16-input-module","title":"Allen-Bradley 1762-IQ16 Input Module","description":"\u003ch2\u003eAllen-Bradley 1762-IQ16 Input Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for discrete signal acquisition in MicroLogix 1200 controller systems, the \u003cstrong\u003eAllen-Bradley 1762-IQ16\u003c\/strong\u003e (\u003cstrong\u003e1762-IQ16\u003c\/strong\u003e Input Module) provides direct electrical signal processing through 16 digital DC inputs. The module supports sink\/source input wiring with 24 VDC field signals and screw terminal connections.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e1762-IQ16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eAllen-Bradley\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.99 lbs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-20 to 65 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e70 mA at 5 VDC maximum bus current draw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eInput Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eMicroLogix 1200\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e16 Digital Inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eSink\/Source Input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Category\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Voltage\u003c\/td\u003e\n\u003ctd\u003e10-30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Off-State Voltage\u003c\/td\u003e\n\u003ctd\u003e5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Off-State Current\u003c\/td\u003e\n\u003ctd\u003e1.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum On-State Voltage\u003c\/td\u003e\n\u003ctd\u003e10 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Input Impedance\u003c\/td\u003e\n\u003ctd\u003e3K Ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Signal Delay\u003c\/td\u003e\n\u003ctd\u003e8 ms on\/off signal delay\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnclosure Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Type\u003c\/td\u003e\n\u003ctd\u003eScrew Terminals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Method\u003c\/td\u003e\n\u003ctd\u003eDIN Rail Mount\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eEtherNet\/IP and Industrial Control Integration Features\u003c\/h3\u003e\n\u003cp\u003eThe 1762-IQ16 provides MicroLogix 1200 I\/O density scaling through a 16-point digital input configuration. The module transfers field device status signals to the controller through the local expansion interface with defined signal delay characteristics.\u003c\/p\u003e\n\u003cp\u003eThe module supports Allen-Bradley PLC system integration with firmware flash compatibility across supported MicroLogix 1200 controller configurations. The input architecture allows sink\/source field wiring selection for different industrial sensor and switch connection methods.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: How many digital input channels are available on the Allen-Bradley 1762-IQ16?\u003cbr\u003eA: The 1762-IQ16 provides 16 digital DC input channels for MicroLogix 1200 controller expansion.\u003c\/p\u003e\n\u003cp\u003eQ: What input voltage range does the 1762-IQ16 support?\u003cbr\u003eA: The module accepts 10-30 VDC input signals within a 24 VDC input category.\u003c\/p\u003e\n\u003cp\u003eQ: What is the maximum input signal delay of the 1762-IQ16?\u003cbr\u003eA: The module has a maximum signal delay of 8 ms for both on and off signal transitions.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the 1762-IQ16 module on the MicroLogix 1200 expansion interface using the specified DIN rail mounting method or approved panel installation arrangement.\u003c\/p\u003e\n\u003cp\u003eConnect field devices according to the sink\/source input wiring configuration requirements. Verify input polarity and terminal assignments before applying 24 VDC field power.\u003c\/p\u003e\n\u003cp\u003eRoute digital input wiring separately from high-voltage power conductors and high-current switching circuits to reduce electrical interference. Maintain proper control panel grounding practices and use shielded wiring where required by the installation environment.\u003c\/p\u003e","brand":"Allen-Bradley","offers":[{"title":"Default Title","offer_id":43655748059226,"sku":"1762-IQ16","price":123.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/1762-IQ161.jpg?v=1784000578","url":"https:\/\/www.plcmasters.com\/products\/allen-bradley-1762-iq16-input-module","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}