Skip to content
Allen-Bradley 1769-IT16 Compact I/O Thermocouple Input Module

Allen-Bradley 1769-IT16 Compact I/O Thermocouple Input Module

  • 16 In stock
  • Manufacturer: Allen-Bradley

  • Product No.: 1769-IT16

  • Condition: In stock

  • Product Type: Compact I/O Thermocouple Input Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 449g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":43664939876442,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"1769-IT16","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Allen-Bradley 1769-IT16 Compact I\/O Thermocouple Input Module","public_title":null,"options":["Default Title"],"price":12300,"weight":449,"compare_at_price":32000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Allen-Bradley 1769-IT16 Compact I/O Thermocouple Input Module

Configured for thermocouple and millivolt temperature signal acquisition in Compact I/O control networks, the Allen-Bradley 1769-IT16 (1769-IT16 Thermocouple/mV Input Module) provides direct electrical measurement of 16 isolated low-level analog input channels for CompactLogix and MicroLogix 1500 systems.

Suffix Breakdown & Model Matrix

Model Reference Description
1769-IT16 Compact I/O thermocouple/mV analog input module
1769 Family Compact I/O module platform
Input Configuration 16 isolated thermocouple/mV input channels

Hardware Specifications

Parameter Specification
Model 1769-IT16
Brand Allen-Bradley
Origin USA
Weight 0.99 lbs
Dimensions 118 mm x 52.5 mm x 87 mm
Operating Temp 0 to 60 deg C
Power Consumption Approximately 4.6 W
Product Type Thermocouple Input Modules
Series Compact I/O 1769 Family
Input Channels 16 isolated analog input channels
Input Types J, K, T, E, R, S, B, N thermocouples; +/-50 mV and +/-100 mV
Resolution 15-bit plus sign
Accuracy +/-0.35% of full scale
Cold Junction Compensation Internal automatic compensation
Input Impedance Greater than 1 MOhm
Common Mode Rejection Greater than 60 dB at 50-60 Hz
Backplane Current Draw 170 mA at 5 VDC; 120 mA at 24 VDC
Isolation Voltage 1200 VAC for 1 s or 1697 VDC for 1 s
Working Voltage 75 VDC (IEC Class 2 reinforced insulation)
Wiring Copper, 22-14 AWG solid; 22-16 AWG stranded
Terminal Block 1769-RTBN18 replacement

EtherNet/IP and I/O Signal Processing Characteristics

The 1769-IT16/A operates as a temperature signal acquisition module within Compact I/O architectures. The module converts thermocouple and millivolt signals through internal analog processing and transfers measurement data through the CompactLogix backplane interface.

The module supports I/O density scaling with 16 temperature input channels in a single Compact I/O slot. Internal cold junction compensation (CJC) processing provides thermocouple reference compensation, while common mode rejection performance reduces external electrical noise influence on low-level sensor signals.

Firmware flash compatibility allows supported CompactLogix and MicroLogix 1500 controllers to identify and manage module configuration parameters during system integration.

Frequently Asked Questions

Q: What thermocouple types are supported by the 1769-IT16?
A: The module supports J, K, T, E, R, S, B, and N thermocouple types, along with +/-50 mV and +/-100 mV millivolt input ranges.

Q: Does the module require an external cold junction compensation device?
A: No. The module includes internal automatic cold junction compensation for thermocouple measurements.

Q: What is the backplane current requirement of the module?
A: The module requires 170 mA at 5 VDC and 120 mA at 24 VDC from the Compact I/O backplane.

Field Installation Guidelines

Install the 1769-IT16 module within the Compact I/O assembly according to controller platform installation procedures. Verify module seating, terminal block engagement, and I/O configuration before applying system power.

Use shielded instrumentation wiring where required for thermocouple and millivolt signal connections. Route low-level temperature sensor wiring separately from power conductors and switching circuits to minimize electrical interference.

Maintain correct thermocouple polarity during wiring installation. Verify sensor type configuration, channel scaling, and diagnostic status through controller software before placing the measurement system into operation.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured