Skip to content
Allen-Bradley 2711-T5A15L1 PanelView 550 Operator Terminal

Allen-Bradley 2711-T5A15L1 PanelView 550 Operator Terminal

  • 16 In stock
  • Manufacturer: Allen-Bradley

  • Product No.: 2711-T5A15L1

  • Condition: In stock

  • Product Type: PanelView 550 Operator Terminal

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1048g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":43867617067098,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"2711-T5A15L1","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Allen-Bradley 2711-T5A15L1 PanelView 550 Operator Terminal","public_title":null,"options":["Default Title"],"price":12300,"weight":1048,"compare_at_price":32000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Allen-Bradley 2711-T5A15L1 PanelView 550 Operator Terminal

The Allen-Bradley 2711-T5A15L1, also cataloged as the 2711-T5A15L1 PanelView 550 Operator Terminal, provides touchscreen HMI operation through ControlNet and RS-232 interfaces.

Hardware Specifications

Parameter Specification
Model 2711-T5A15L1
Brand Allen-Bradley
Product Type PanelView 550 Operator Terminal
Product Family PanelView Standard Terminals
Product Line PanelView 550
Series A, B, C, D, E, F, G, H
Weight 2.31 lb
Operating Temp 0 to 55 deg C
Power Consumption 20 W heat dissipation; separate input power consumption value not specified
Nominal Input Supply 24 VDC
Input Voltage Range 18 to 32 VDC
Display Size 5.5 in
Display Type Monochrome LCD, blue mode
Display Area 120 x 60 mm
Resolution 256 x 128 pixels
Input Type Touchscreen
Touch Cell Size 26 x 30 pixels
Touch Actuation Rating 1 million presses
Backlight LED, 100,000 hr stated life
Application Runtime Memory 170 KB
Nonvolatile Memory 240 KB
Communication Ports 1 x ControlNet; 1 x RS-232 printer interface
Communication Cable 2711-NC13
Memory Card 2711-NM232
Time Clock Battery 2711-NB4 Operator Interface
Enclosure Rating NEMA Type 12/13, Type 4X indoor use, IP54, IP65
Heat Dissipation 20 W, 69 BTU/hr

PanelView 550 ControlNet and HMI Interface

The 2711-T5A15L1 combines a monochrome 256 x 128 pixel LCD with a touch-based operator interface. The display area measures 120 x 60 mm, while the touch interface uses defined touch cells for operator actuation.

ControlNet provides the primary network communication interface specified for this terminal. An additional RS-232 port provides printer-interface connectivity.

The terminal accepts a nominal 24 VDC supply across an 18 to 32 VDC input range. Wiring should maintain the specified DC polarity and supply voltage at the terminal input.

Application storage includes 170 KB of runtime memory and 240 KB of nonvolatile memory for application objects, text, and bitmaps. The 2711-NM232 memory card is specified as the removable memory option.

Frequently Asked Questions (FAQ)

Q: What DC supply voltage does the 2711-T5A15L1 require?
A: The nominal input supply is 24 VDC, with a specified operating input range of 18 to 32 VDC.

Q: Which communication interfaces are provided on this PanelView terminal?
A: The terminal provides one ControlNet communication port and one RS-232 printer interface.

Q: What display and touch hardware does the terminal use?
A: It uses a 5.5 in monochrome LCD with 256 x 128 pixel resolution and touchscreen input.

Field Installation Guidelines

  • Verify the DC supply remains within the specified 18 to 32 VDC input range before energizing the terminal.
  • Use wiring with appropriate insulation ratings and route DC power separately from high-energy switching conductors.
  • Maintain correct supply polarity and provide suitable upstream overcurrent protection according to the installation design.
  • Install the terminal within the specified 0 to 55 deg C operating temperature range.
  • Confirm the panel cutout and rear clearance accommodate the stated installed depth and memory-card access requirements.
  • Maintain enclosure sealing practices consistent with the required NEMA and IP protection level.
  • Route ControlNet communication wiring separately from high-voltage power and high-current switching conductors.
  • Follow the applicable ControlNet cable and termination requirements for the installed network topology.
  • Connect the RS-232 interface according to the required printer-interface pinout and cable specification.
  • Where shielded communication cables are used, terminate shields according to the system grounding design and applicable installation standards.
  • Do not perform wiring changes while energized unless the installation procedure and equipment documentation explicitly permit such work.
  • Verify touchscreen operation and communication status after installation before placing the terminal into normal service.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products