Allen Bradley 2711-T9C8 PanelView 900 Standard Operator Terminal
Configured for operator touch input and display functions in PanelView Standard systems, the Allen Bradley 2711-T9C8 (2711-T9C8 PanelView 900 Standard Operator Terminal) provides direct physical interface execution. It uses an active matrix color display, resistive touchscreen, Data Highway Plus communication, and RS-232 printer connectivity.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 2711-T9C8 |
| Brand | Allen Bradley |
| Product Type | PanelView 900 Standard Operator Terminal |
| Product Line | PanelView 900 |
| Product Family | PanelView Standard Terminals |
| Series | A, B, C, D, E, F |
| Weight | 7.00 lb |
| Display Size | 9 in |
| Display Type | Active Matrix Thin-Film Resistor (TFT) with Cold Cathode Fluorescent (CCF) backlight |
| Display Color | Color |
| Display Area | 210 x 131 mm (8.27 x 5.17 in) |
| Resolution | 640 x 480 pixels |
| Input Type | Touch |
| Touchscreen | 384 cells, arranged as 24 columns x 16 rows |
| Touch Cell Size | 26 x 30 pixels |
| Application Memory | 240K bytes prior to Series E; 1008K bytes for Series E |
| Communication Ports | Data Highway Plus (DH+); RS-232 printer |
| Communication Cable | 2711-NC13 |
| Input Voltage Range | 85-264 VAC, 47-63 Hz |
| Nominal Input Power | 120 VAC |
| Operating Temperature | 0-55 deg C (32-131 deg F) |
| Power Consumption / Heat Dissipation | 39 W (132 BTU/HR) |
| Backlight | 100,000 hr LED backlight life, as supplied |
| Memory | 1008K bytes, as supplied |
| Communication | DH+ and RS-232 printer |
PanelView 900 Display and Communication Characteristics
The 2711-T9C8 provides a 640 x 480 pixel color display with a 210 x 131 mm active viewing area. The operator interface uses a resistive touchscreen with 384 touch cells arranged across the display matrix. Application memory differs by terminal series, with 240K bytes specified before Series E and 1008K bytes specified for Series E. Communication interfaces include Data Highway Plus and an RS-232 printer port. The specified communication cable is Allen Bradley 2711-NC13.
The supplied data identifies the display as TFT with CCF backlighting while separately specifying 100,000 hr LED backlight life. These source entries should be verified against the terminal revision before replacement or refurbishment.
Frequently Asked Questions
Q: What input power range is specified for the 2711-T9C8?
A: The terminal accepts 85-264 VAC at 47-63 Hz, with 120 VAC listed as nominal input power.
Q: Which communication interfaces are available on the terminal?
A: The terminal provides Data Highway Plus for system communication and RS-232 connectivity for printer interfacing.
Q: Does application memory vary between terminal series?
A: Yes. Supplied data specifies 240K bytes before Series E and 1008K bytes for Series E terminals.
Field Installation Guidelines
- Verify the terminal catalog number and series before installation because supplied memory and display data varies by revision.
- Confirm the available AC supply remains within the specified 85-264 VAC input range before energizing.
- Route AC power wiring separately from communication cables to reduce conducted and radiated interference.
- Maintain proper protective grounding according to the installation enclosure and applicable electrical standards.
- Keep DH+ communication wiring separated from high-current motor, contactor, and switching-device conductors.
- Use the specified 2711-NC13 communication cable where the installation requires that cable designation.
- Ensure touchscreen and display surfaces remain mechanically protected during panel installation and commissioning.
- Verify connector seating and cable strain relief before applying power to the terminal.
- Confirm environmental conditions remain within the specified 0-55 deg C operating temperature range.
- Do not assume hot-swap capability unless the applicable PanelView documentation explicitly permits energized module replacement.
- Inspect the terminal display, touchscreen response, communication status, and printer interface during commissioning.
- Where shielded communication wiring is used, terminate shields according to the network installation standard without creating unintended ground loops.
Features
We welcome bulk orders and have a minimum order quantity of just one unit.
Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.
For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.
We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.
We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.
Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.