Description
Allen-Bradley 2711P-K4M20D8 PanelView Plus 6 400 Operator Terminal
Configured for keypad-based operator input and Ethernet/RS-232 data communication in the PanelView Plus 6 platform, the Allen-Bradley 2711P-K4M20D8 (2711P-K4 400 Operator Terminal) provides a 3.5 in. grayscale TFT LCD interface with 320 x 240 resolution, DC input, Ethernet, RS-232, and USB peripheral connectivity.
Suffix Breakdown & Model Matrix
| Model Element | Specification |
|---|---|
| Bulletin | 2711P |
| Input Type | K = Keypad |
| Terminal Size | 4 = 400 class, 3.5 in. display |
| Display Type | M = Grayscale |
| Communication | 20 = Ethernet, RS-232, and USB |
| Power | D = DC input |
| Operating System | 8 = Windows CE 6.0 |
| Complete Catalog Number | 2711P-K4M20D8 |
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 2711P-K4M20D8 |
| Brand | Allen-Bradley |
| Product Type | PanelView Plus 6 400 Operator Terminal |
| Series | PanelView Plus 6 |
| Origin | United States of America |
| Weight | 1.31 lb |
| Input Voltage | 18-32 VDC |
| Input Power Range | 18-30 VDC |
| Display Size | 3.5 in. |
| Display Type | Grayscale TFT LCD |
| Display Area | 70 x 53 mm |
| Resolution | 320 x 240 |
| Gray Levels | 16 |
| Display Color | Monochrome |
| Backlight | White LED, non-replaceable |
| Backlight Life | 25,000 h minimum at 25 deg C |
| Operator Input | Keypad |
| Function Keys | 8, F1-F8 |
| Keypad Rating | 1 million presses |
| RAM | 256 MB |
| Nonvolatile Memory | 512 MB |
| Approx. Free User Memory | 79 MB |
| Ethernet | Integrated |
| RS-232 | Integrated |
| USB | 2 peripheral ports |
| Communication Cable | 2711-NC13 |
| Operating System | Windows CE 6.0 |
| Lifecycle Status | End of life / discontinued |
Industrial Control and Firmware Compatibility
The 2711P-K4M20D8 uses an integrated Ethernet interface together with RS-232 and USB ports for external device communication. The supplied data does not identify a specific Ethernet protocol or deterministic network class, so protocol performance must be evaluated against the connected controller and application configuration.
Firmware flash compatibility is dependent on the PanelView Plus 6 terminal firmware and installed runtime environment. Firmware files should be matched to the exact terminal catalog number and applicable software revision before an upgrade or replacement operation. The supplied data does not specify a firmware revision for this unit.
The terminal provides 256 MB RAM and approximately 512 MB of nonvolatile memory, with approximately 79 MB identified as free user memory in the supplied specifications.
Frequently Asked Questions (FAQ)
Q: What DC supply range is specified for the 2711P-K4M20D8?
A: The supplied specifications identify an input voltage range of 18-32 VDC and an input power range of 18-30 VDC. The actual installation supply should remain within the applicable manufacturer limits.
Q: What physical operator input is provided?
A: The terminal uses a keypad with 8 function keys, designated F1 through F8. The supplied keypad specification is 1 million presses.
Q: Does the terminal provide Ethernet and RS-232 communication simultaneously?
A: The catalog configuration identifies Ethernet and RS-232 as integrated communication interfaces, with two USB peripheral ports also provided.
Field Installation Guidelines
- Verify the catalog number 2711P-K4M20D8 before installation because PanelView Plus 6 variants differ in display, communication, input, and power configurations.
- Confirm that the external DC supply is within the specified input voltage range before energizing the terminal.
- Route DC power wiring separately from high-voltage switching conductors and high-current motor wiring where practical.
- Keep communication wiring away from sources of electromagnetic interference and avoid unnecessary parallel routing with power conductors.
- Terminate cable shields according to the applicable control-system grounding design and plant electrical standards.
- Verify Ethernet and RS-232 pin assignments and cable type before connecting external equipment.
- Do not apply USB peripheral connections until the connected device has been confirmed compatible with the terminal operating environment.
- Provide adequate panel clearance for connector access and cable bend radius.
- Do not substitute a different PanelView Plus catalog variant solely on the basis of physical display size; communication, power, and input configurations must also match.
- The supplied data contains conflicting weight values, with 1.31 lb (0.60 kg) in the detailed specification table and 1.06 lb in the additional notes. Verify the physical unit or applicable manufacturer documentation before using weight for mechanical design.
Features
We welcome bulk orders and have a minimum order quantity of just one unit.
Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.
For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.
We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.
We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.
Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.