{"product_id":"allen-bradley-2711p-t12c4a8-panelview-plus-6-1250-operator-terminal","title":"Allen-Bradley 2711P-T12C4A8 PanelView Plus 6 1250 Operator Terminal","description":"\u003ch2\u003eAllen-Bradley 2711P-T12C4A8 PanelView Plus 6 1250 Operator Terminal\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eAllen-Bradley 2711P-T12C4A8\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003e2711P-T12\u003c\/strong\u003e PanelView Plus 6 operator terminal, provides touchscreen operator input, color TFT visualization, and Ethernet or RS-232 communication. The terminal accepts 100-240 VAC at 50-60 Hz and provides two USB host ports for connected peripherals.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e2711P-T12C4A8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eAllen-Bradley\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003ePanelView Plus 6\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003e1250 Operator Terminal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eA and B Operator Interface\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e6 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e100-240 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Frequency\u003c\/td\u003e\n\u003ctd\u003e50-60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDisplay Size\u003c\/td\u003e\n\u003ctd\u003e12.1 in\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDisplay Type\u003c\/td\u003e\n\u003ctd\u003eColor active-matrix TFT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDisplay Area\u003c\/td\u003e\n\u003ctd\u003e246 x 184 mm (9.7 x 7.2 in.)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e800 x 600 pixels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eColor Depth\u003c\/td\u003e\n\u003ctd\u003e18-bit color graphics\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperator Input\u003c\/td\u003e\n\u003ctd\u003eTouchscreen\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTouch Rating\u003c\/td\u003e\n\u003ctd\u003e1 million presses\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBacklight\u003c\/td\u003e\n\u003ctd\u003eCCFL, 50,000 hours minimum at 25 deg C; field replaceable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInternal Flash Memory\u003c\/td\u003e\n\u003ctd\u003e512 MB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRAM\u003c\/td\u003e\n\u003ctd\u003e512 MB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIntegrated Ports\u003c\/td\u003e\n\u003ctd\u003eEthernet, RS-232, 2 USB host\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication\u003c\/td\u003e\n\u003ctd\u003eEthernet and RS-232\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Cable\u003c\/td\u003e\n\u003ctd\u003e2711-NC13\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating System\u003c\/td\u003e\n\u003ctd\u003eWindows CE 6\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLifecycle Status\u003c\/td\u003e\n\u003ctd\u003eEnd of life\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003ePanelView Plus 6 Communication and Hardware Interface\u003c\/h3\u003e\n\u003cp\u003eThe 2711P-T12C4A8 provides Ethernet and RS-232 interfaces for controller communication and terminal data exchange. Two USB host ports support compatible peripheral connections, while the touchscreen provides direct operator input.\u003c\/p\u003e\n\u003cp\u003eThe 12.1 in color active-matrix TFT uses an 800 x 600 pixel resolution with 18-bit color graphics. Its CCFL backlight is field replaceable and has a specified minimum life of 50,000 hours at 25 deg C.\u003c\/p\u003e\n\u003cp\u003eThe terminal uses 512 MB Flash memory and 512 MB RAM with Windows CE 6. The specified input supply is 100-240 VAC at 50-60 Hz.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: What communication interfaces are integrated into the 2711P-T12C4A8?\u003c\/p\u003e\n\u003cp\u003eA: The terminal integrates Ethernet, RS-232, and two USB host ports for communication and peripheral connectivity.\u003c\/p\u003e\n\u003cp\u003eQ: What display and operator input hardware does this terminal provide?\u003c\/p\u003e\n\u003cp\u003eA: It provides a 12.1 in color active-matrix TFT display with 800 x 600 resolution and touchscreen input.\u003c\/p\u003e\n\u003cp\u003eQ: Does the supplied data specify the terminal power consumption?\u003c\/p\u003e\n\u003cp\u003eA: No. The supplied documentation specifies the 100-240 VAC input range and 50-60 Hz frequency, but not consumption.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the terminal in a panel opening that matches the manufacturer-defined mechanical requirements for the PanelView Plus 6 enclosure.\u003c\/p\u003e\n\u003cp\u003eVerify the incoming AC supply remains within the specified 100-240 VAC range and 50-60 Hz frequency before energization.\u003c\/p\u003e\n\u003cp\u003eRoute AC power wiring separately from low-level communication wiring where practical to reduce conducted and radiated interference.\u003c\/p\u003e\n\u003cp\u003eUse appropriate protective grounding and follow the applicable electrical installation standard for the control panel.\u003c\/p\u003e\n\u003cp\u003eKeep Ethernet and RS-232 communication cables separated from high-current switching conductors and motor power cables.\u003c\/p\u003e\n\u003cp\u003eTerminate cable shields according to the control-system grounding architecture and avoid creating unintended ground-current paths.\u003c\/p\u003e\n\u003cp\u003eConnect USB peripherals only when their electrical characteristics and installation requirements are compatible with the terminal.\u003c\/p\u003e\n\u003cp\u003eInspect the touchscreen and display area after installation to ensure the operator interface remains unobstructed.\u003c\/p\u003e\n\u003cp\u003eBecause the supplied lifecycle status is end of life, verify system compatibility and replacement requirements before integrating the terminal into a new control installation.\u003c\/p\u003e","brand":"Allen-Bradley","offers":[{"title":"Default Title","offer_id":43856225599578,"sku":"2711P-T12C4A8","price":123.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/2711P-T12C4A8.jpg?v=1786952494","url":"https:\/\/www.plcmasters.com\/products\/allen-bradley-2711p-t12c4a8-panelview-plus-6-1250-operator-terminal","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}