{"id":43833413697626,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"2711PC-K4M20D8","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Allen-Bradley 2711PC-K4M20D8 PanelView Plus Compact 400 Operator Interface","public_title":null,"options":["Default Title"],"price":12300,"weight":540,"compare_at_price":32000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Allen-Bradley 2711PC-K4M20D8 PanelView Plus Compact 400 Operator Interface

Configured for operator monitoring and control in Allen-Bradley controller systems, the Allen-Bradley 2711PC-K4M20D8 (2711PC-K4M20D8 PanelView Plus Compact 400 Operator Interface) provides keypad-based operator input, monochrome graphical display output, and Ethernet/serial communication.

Hardware Specifications

Parameter Specification
Model 2711PC-K4M20D8
Brand Allen-Bradley / Rockwell Automation
Product Family PanelView Plus Compact 400
Product Type Keypad Operator Interface
Display 3.5 in monochrome grayscale STN
Resolution 320 x 240 pixels, QVGA
Operator Input 8 tactile function keys, F1-F8
Input Voltage 24 VDC nominal
Operating Voltage Range 18-32 VDC
Power Consumption 25 W maximum; 1.0 A at 24 VDC
Ethernet 1 x 10/100 Mbps Ethernet
Serial Communication 1 x RS-232; DF1 or DH-485
USB 1 x USB host port
Internal Memory 64 MB RAM; 64 MB non-volatile flash
Software Platform FactoryTalk View Studio Machine Edition (Compact)
Application Capacity Up to 25 displays and 200 alarm messages
Operating Temperature 0 deg C to 55 deg C
Weight 1.19 lb
Firmware Environment Windows CE 6

Industrial Control and Communication Characteristics

The 2711PC-K4M20D8 provides Ethernet and RS-232 interfaces for controller and network communication. The RS-232 interface supports DF1 or DH-485 protocols. Ethernet operates at 10/100 Mbps for network connectivity.

The keypad provides eight physical function keys, while the 320 x 240 pixel monochrome STN display presents operator interface screens. The specified 24 VDC supply operates across an 18-32 VDC input range, with maximum power consumption of 25 W.

FactoryTalk View Studio Machine Edition (Compact) is the specified engineering environment. The supplied data identifies application support for up to 25 displays and 200 alarm messages.

Frequently Asked Questions (FAQ)

Q: What power supply does the 2711PC-K4M20D8 require?
A: The unit uses a 24 VDC nominal supply and has a specified operating range of 18-32 VDC.

Q: Which communication interfaces are provided?
A: The unit provides one 10/100 Mbps Ethernet port, one RS-232 serial port supporting DF1 or DH-485, and one USB host port.

Q: What operator input hardware is installed?
A: The operator interface uses eight tactile function keys designated F1 through F8.

Field Installation Guidelines

Install the operator interface in a panel cutout that matches the manufacturer's mechanical installation requirements. Confirm adequate clearance for the enclosure, connectors, cable bend radius, and operator access before mounting.

Connect the 24 VDC supply with correct polarity and verify that the supply remains within the specified 18-32 VDC operating range. Provide appropriate overcurrent protection in accordance with the installation design.

Route Ethernet and RS-232 communication wiring separately from high-voltage and high-current conductors where practical to reduce conducted and radiated electrical interference. Use appropriate shield termination and grounding practices for the selected cable and plant grounding scheme.

Verify the selected serial protocol, DF1 or DH-485, before commissioning. Confirm Ethernet configuration and controller communication parameters before placing the operator interface into service.

For maintenance, isolate electrical power before disconnecting field wiring. Do not connect or disconnect communication cables unless the applicable installation and equipment procedures permit the operation.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products