Skip to content
Allen-Bradley 4601-RIO-MCM Remote I/O Modbus Communication Module

Allen-Bradley 4601-RIO-MCM Remote I/O Modbus Communication Module

  • 16 In stock
  • Manufacturer: AMPHENOL

  • Product No.: 4601-RIO-MCM

  • Condition: In stock

  • Product Type: Remote I/O Modbus Communication Module

  • Payment:T/T, Western Union

  • Weight: 240g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":43983937568858,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"4601-RIO-MCM","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Allen-Bradley 4601-RIO-MCM Remote I\/O Modbus Communication Module","public_title":null,"options":["Default Title"],"price":12300,"weight":240,"compare_at_price":32000,"inventory_management":"shopify","barcode":null,"requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Configured for Remote I/O data exchange and Modbus master communication in industrial control networks, the Allen-Bradley 4601-RIO-MCM (4601-RIO-MCM Remote I/O Modbus Communication Module) provides direct physical and electrical execution between PLC systems and serial field devices.

Hardware Specifications

Parameter Specification
Model 4601-RIO-MCM
Brand Allen-Bradley
Origin United States
Weight 0.24 kg
Operating Temp 0 deg C to 60 deg C
Power Consumption 18.36 VDC, 500 mA
Module Type Remote I/O to Modbus Master Communication Module
Primary Protocol Allen-Bradley Remote I/O (RIO)
Secondary Protocol Modbus RTU / Modbus ASCII Master
Communication Ports RS-232 / RS-422 / RS-485 selectable
Modbus Device Capacity Up to 32 Modbus slave devices per channel
Modbus Baud Rate 300 bps to 38.4 kbps
RIO Communication Rate 57.6k, 115.2k, 230.4k bps
Mounting Type DIN Rail / Chassis Mount
Operating Humidity 5% to 95% RH, non-condensing
LED Indicators Power, Module Status, RIO Network Activity, Serial Rx/Tx Activity

EtherNet/IP and Industrial Communication Integration

The Allen-Bradley 4601-RIO-MCM operates as a protocol conversion interface between Remote I/O networks and Modbus serial devices. The module processes serial communication frames through RS-232, RS-422, or RS-485 interfaces while exchanging mapped data with Allen-Bradley PLC architectures.

The module supports deterministic Remote I/O communication rates and Modbus master polling functions for connected field devices. Firmware flash compatibility should be verified before replacement installation to maintain communication configuration consistency.

I/O data mapping must be configured according to PLC memory allocation requirements and connected Modbus register definitions. Shielded communication wiring is required to reduce electromagnetic interference during serial data transmission.

Frequently Asked Questions

Q: Does the 4601-RIO-MCM support Modbus slave operation?

A: The provided specifications define Modbus RTU and Modbus ASCII operation in Master Mode. Slave functionality is not specified.

Q: What serial interfaces are available for field device connection?

A: The module supports selectable RS-232, RS-422, and RS-485 serial communication interfaces.

Q: Can the module communicate with multiple Modbus devices?

A: The module supports communication with up to 32 Modbus slave devices per channel according to the provided technical data.

Field Installation Guidelines

Install the module on a compatible DIN rail or chassis mounting location with sufficient clearance for wiring access and status indicator visibility.

Connect RS-485 wiring using proper polarity and maintain separation between communication cables and high-voltage power conductors. Apply cable shielding and terminate the shield according to site grounding standards.

Verify the Remote I/O network addressing, baud rate settings, and Modbus register mapping before commissioning. Confirm power supply wiring polarity and measure operating voltage before connecting communication devices.

Avoid routing serial communication cables parallel to motor power lines, variable frequency drive outputs, or high-current switching circuits to reduce electrical noise interference.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.