Description
Allen-Bradley SWTC-SPIDER5TX Unmanaged 5-Port Ethernet Switch
Configured for unmanaged Fast Ethernet connectivity in industrial control networks, the Allen-Bradley SWTC-SPIDER5TX (SWTC-SPIDER5TX unmanaged Ethernet switch) provides direct physical network interconnection through five 10/100Base-TX RJ45 ports. The unit supports auto-negotiation, Auto-MDI/MDI-X, IEEE 802.3, IEEE 802.3u, and IEEE 802.3x functions.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | SWTC-SPIDER5TX |
| Brand | Allen-Bradley |
| Product Type | Unmanaged 5-port Fast Ethernet Switch |
| Dimensions | 25 mm x 114 mm x 79 mm |
| Operating Temp | 0 deg C to +60 deg C |
| Power Consumption | Approx. 2.2 W; approximately 90 mA at 24 VDC |
| Ethernet Ports | 5 x 10/100Base-TX, RJ45 |
| Network Standards | IEEE 802.3, IEEE 802.3u, IEEE 802.3x |
| Transmission Mode | Auto-Negotiation, Auto-MDI/MDI-X |
| Input Voltage | 12 VDC to 24 VDC |
| Operating Voltage Range | 9.6 VDC to 32 VDC |
| Power Inputs | Redundant / dual power inputs |
| Storage Temperature | -40 deg C to +70 deg C |
| Relative Humidity | 10% to 95%, non-condensing |
| Housing Material | High-impact polycarbonate/plastic |
| Protection Class | IP30 |
| Mounting | 35 mm DIN rail |
| Cooling | Fanless |
Industrial Ethernet Network Characteristics
The SWTC-SPIDER5TX uses unmanaged switching, so Ethernet forwarding requires no software configuration or switch-management parameters. The five RJ45 ports support 10Base-T and 100Base-TX operation with automatic speed negotiation.
Auto-MDI/MDI-X provides automatic transmit and receive pair adaptation at each copper port. Therefore, separate straight-through and crossover cable selection is not required for normal Ethernet connections.
The switch supports IEEE 802.3x flow control for compatible Ethernet traffic conditions. Front-panel LEDs provide local indication of power, link status, and network activity.
For Allen-Bradley control architectures, the unit can provide physical Ethernet connectivity between compatible controllers, I/O devices, operator interfaces, and other Ethernet nodes. Network-level determinism depends on the connected devices, traffic architecture, and application configuration rather than the unmanaged switch alone.
The dual power-input arrangement supports connection to separate DC supply paths where the installation design requires redundant power feeding. The supplied data does not specify switching behavior or transfer time between power inputs.
Frequently Asked Questions
Q: Does the SWTC-SPIDER5TX require software configuration?
A: No. The supplied specifications identify the unit as an unmanaged switch with plug-and-play operation.
Q: What Ethernet cabling functions are provided by the RJ45 ports?
A: The ports support 10/100Base-TX Ethernet, Auto-Negotiation, and Auto-MDI/MDI-X operation.
Q: Can the switch be installed on a DIN rail?
A: Yes. The specified mechanical mounting method is a 35 mm DIN rail.
Field Installation Guidelines
Install the switch on a mechanically secure 35 mm DIN rail position inside the control cabinet.
Verify the DC supply voltage remains within the specified 9.6 VDC to 32 VDC operating range before energizing the unit.
Use appropriately rated industrial Ethernet cabling and maintain physical separation between communication cables and high-current or high-voltage conductors.
Avoid routing Ethernet cables parallel to motor feeders, contactor wiring, variable-frequency drive output cables, or other strong electromagnetic noise sources.
Terminate cable shields according to the cabinet grounding architecture and applicable site EMC practices. Avoid creating unintended ground-current paths through multiple shield termination points.
Provide sufficient clearance around connected cables to prevent excessive bending or mechanical loading at the RJ45 connectors.
Maintain the specified operating temperature and humidity conditions, and prevent condensation inside the enclosure.
Because the housing is rated IP30, install the switch inside an enclosure providing the environmental protection required by the installation location.
Verify link LEDs and power indicators after wiring. Confirm network communication at the connected control devices before placing the Ethernet segment into service.
Features
We welcome bulk orders and have a minimum order quantity of just one unit.
Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.
For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.
We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.
We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.
Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.