{"id":42334029873242,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"SE4302T01 KL3002X1-BA1","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Emerson SE4302T01 KL3002X1-BA1 DO 24 VDC High Side CHARM","public_title":null,"options":["Default Title"],"price":17800,"weight":1361,"compare_at_price":39000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[]}

Description

Overview

The Emerson SE4302T01 KL3002X1-BA1 is a 24 VDC high-side digital output CHARM module. It controls solenoids, valves, and relays in industrial automation systems. Its compact, pluggable design allows flexible installation and easy maintenance. The module works in hazardous and non-hazardous zones with proper precautions. Keying ensures correct CHARM-to-terminal block connection. No calibration is required, simplifying operation.

Technical Specifications

  • Model: SE4302T01

  • CHARM Type: KL3002X1-BA1

  • Function: Digital Output – High-Side Switching

  • Voltage Rating: 24 VDC

  • Output Type: High-side switch (switches positive side of load)

  • Typical Load Types: Solenoids, relays, valves, and other inductive loads

  • Installation Zone: Zone 2 hazardous areas (with precautions)

  • System Compatibility: DeltaV™ CHARM I/O subsystem

  • Device Type: 24 V DC solenoid coils

  • On-State Output Rating: 100 mA continuous @ 24 V DC

  • Off-State Leakage Current: 1 mA maximum

  • Line Fault Detection:

    • Short circuit: <50 Ω load

    • Good status: 240 Ω to 10 kΩ load

    • Open circuit: >20 kΩ load

  • Configurable Output Behavior: Momentary output, continuous pulse output, line fault testing

  • Line Fault Test Timing: 200 µsec

  • Field Circuit Protection: 200 mA current limiting, field wiring disconnect

  • CHARM Power Requirement:

    • 116 mA max @ 24 V DC (standard terminal block)

    • 24 mA max @ 24 V DC (relay output terminal block)

  • CHARM Heat Dissipation: Pulse train 0.1 Hz to 10 kHz, 50 µsec minimum pulse width

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products