{"id":42334045503578,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"SE4303T03 KL3031X1-BA1","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Emerson SE4303T03 KL3031X1-BA1 RTD \/ Resistance Input CHARM","public_title":null,"options":["Default Title"],"price":17800,"weight":454,"compare_at_price":39000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[]}

Description

Overview

The Emerson SE4303T03 KL3031X1-BA1 is an RTD Input CHARM module for DeltaV™ Electronic Marshalling systems. It measures temperature accurately using RTD sensors, supporting industrial applications that require precise thermal monitoring. The module ensures reliable readings and signal integrity, making it ideal for critical process control environments. Its pluggable design allows easy installation and integration into existing DeltaV™ systems. Built-in diagnostics detect open circuits and validate input signals for operational safety. The module also supports Zone 2 hazardous area installation when following proper guidelines.

Technical Specifications

  • Model: SE4303T03

  • CHARM Type: KL3031X1-BA1

  • Function: RTD input for temperature measurement

  • Supported RTD Types: Pt100, Pt1000, and other standard RTDs

  • Measurement Range: -200°C to +850°C (typical for Pt100)

  • Accuracy: High-resolution input for precise readings

  • Input Isolation: Galvanically isolated to prevent ground loops

  • Cold Junction Compensation: Not required for RTDs

  • Installation: Pluggable into CHARM I/O cards; DeltaV™ compatible

  • Diagnostics: Open circuit detection and signal validation included

  • Zone Compatibility: Suitable for Zone 2 hazardous areas (per guidelines)

Power Specifications

  • CHARM Bus Power: +6.3 VDC at 32 mA

  • Field Circuit Power: +24 VDC at 10 mA

Environmental Specifications

  • Ambient Temperature: -40 °C to +70 °C

  • Shock: 10 g half-sine wave, 11 ms

  • Vibration: 1 mm peak-to-peak from 2–13.2 Hz; 0.7 g from 13.2–150 Hz

  • Airborne Contaminants: ISA-S71.04 –1985 Class G3

  • Relative Humidity: 5 to 95% non-condensing

  • Terminal Block Key Position: 3ARTD / Resistance Input

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products