{"product_id":"ge-is200emioh1a-ex2100-exciter-main-i-o-board","title":"GE IS200EMIOH1A EX2100 Exciter Main I\/O Board","description":"\u003cp\u003eThe GE IS200EMIOH1A is an Exciter Main Input\/Output (EMIO) Board manufactured by General Electric for the EX2100 excitation control system. It is a single-slot, double-height VME-style board installed in the control rack. The board manages I\/O signals from multiple exciter terminal boards, including contact inputs, PT and CT signals, relay drivers, and gate pulse signal communication with the ESEL board.\u003c\/p\u003e\n\u003ch3\u003eFunctional Description\u003c\/h3\u003e\n\u003cp\u003eThe IS200EMIOH1A serves as the main I\/O interface between the EX2100 control rack and its associated terminal boards. It handles signals from the ECTB, EACF, EXTB, and EPCT terminal boards, coordinating the transfer of input and output signals within the excitation control system.\u003c\/p\u003e\n\u003cp\u003eIts I\/O functions include:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eProcessing contact input signals.\u003c\/li\u003e\n\u003cli\u003eHandling potential transformer (PT) and current transformer (CT) signals.\u003c\/li\u003e\n\u003cli\u003eControlling output relay drivers and pilot trip relay drivers.\u003c\/li\u003e\n\u003cli\u003eSending logic-level gate pulse signals through the backplane to the ESEL board.\u003c\/li\u003e\n\u003cli\u003eSupporting de-excitation control through its interface with the EXTB terminal board and associated EDEX circuitry.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eBackplane Interface and Signal Connections\u003c\/h3\u003e\n\u003cp\u003eThe board uses the control backplane (EBKP) for its electrical connections rather than direct cable connectors mounted on the board. Connector P1 provides communication with other control boards through the backplane, while P2 interfaces with I\/O signals through cable connections located in the lower section of the EBKP.\u003c\/p\u003e\n\u003cp\u003eGate pulse signals are passed from the EMIO board to the ESEL board, which forwards them to the EGPA board in the power conversion cabinet. This signal path connects the control rack's excitation logic with the power conversion section.\u003c\/p\u003e\n\u003ch3\u003eStatus Indicators\u003c\/h3\u003e\n\u003cp\u003eThe IS200EMIOH1A has two LEDs mounted on its front plate:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003ePower LED: Connected to the 5 V DC power supply, indicating the board's power status.\u003c\/li\u003e\n\u003cli\u003eStatus LED: Connected to the FPGA IMOK output, providing a board status indication.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe board has no onboard jumpers, fuses, or cable connectors. Its I\/O connections are routed through the EBKP backplane.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIS200EMIOH1A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric (GE)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eEX2100\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eExciter Main I\/O Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBoard Type\u003c\/td\u003e\n\u003ctd\u003eVME-style printed circuit board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eForm Factor\u003c\/td\u003e\n\u003ctd\u003eSingle-slot, double-height\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Location\u003c\/td\u003e\n\u003ctd\u003eEX2100 control rack\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eI\/O Terminal Boards\u003c\/td\u003e\n\u003ctd\u003eEPCT, ECTB, EACF, EXTB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Types\u003c\/td\u003e\n\u003ctd\u003ePT, CT, contact inputs, relay drivers, gate pulse signals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackplane Interface\u003c\/td\u003e\n\u003ctd\u003eP1 and P2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Indicator\u003c\/td\u003e\n\u003ctd\u003eGreen LED, 5 V DC supply\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indicator\u003c\/td\u003e\n\u003ctd\u003eGreen LED, FPGA IMOK output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of LEDs\u003c\/td\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOnboard Jumpers\u003c\/td\u003e\n\u003ctd\u003eNone\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOnboard Fuses\u003c\/td\u003e\n\u003ctd\u003eNone\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e9.25 x 6.5 inches\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003eApproximately 2 lbs (0.91 kg)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd\u003eUnited States of America (USA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInstruction Manual\u003c\/td\u003e\n\u003ctd\u003eGEI-100453\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eRack Installation and Replacement Considerations\u003c\/h3\u003e\n\u003cp\u003eThe IS200EMIOH1A is designed for a specific position in the EX2100 control rack. Its slot assignment must be checked before installation because inserting the board into an incorrect rack position can damage the electronics.\u003c\/p\u003e\n\u003cp\u003eFor redundant EX2100 control configurations, GEI-100453 describes an online replacement procedure. A failed EMIO board can be replaced while the exciter continues operating on the two remaining controllers. However, a second EMIO failure during this condition can cause an exciter shutdown. This procedure should not be interpreted as unrestricted hot swapping in every EX2100 configuration.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Which terminal boards interface with the GE IS200EMIOH1A?\u003c\/p\u003e\n\u003cp\u003eA: The EMIO board manages I\/O associated with the EPCT, ECTB, EACF, and EXTB terminal boards. These interfaces cover voltage and current feedback, contact inputs, relay control, and excitation-related signals.\u003c\/p\u003e\n\u003cp\u003eQ: How does the IS200EMIOH1A communicate with the EGPA board?\u003c\/p\u003e\n\u003cp\u003eA: The EMIO sends logic-level gate pulse signals through the control backplane to the ESEL board. The ESEL then distributes the signals to the EGPA board in the power conversion cabinet.\u003c\/p\u003e\n\u003cp\u003eQ: Can the IS200EMIOH1A be replaced while the EX2100 exciter is running?\u003c\/p\u003e\n\u003cp\u003eA: Online replacement is documented for redundant control configurations. The failed board can be replaced while the remaining two controllers maintain operation, but the procedure requires attention to the controller status and replacement sequence. Confirm the system configuration and applicable GE instructions before replacement.\u003c\/p\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":67954581340250,"sku":"IS200EMIOH1A","price":175.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/IS200EMIOH1AFB.jpg?v=1750667620","url":"https:\/\/www.plcmasters.com\/products\/ge-is200emioh1a-ex2100-exciter-main-i-o-board","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}