Skip to content
Honeywell 10208/2/1 Relay Output Module

Honeywell 10208/2/1 Relay Output Module

  • 15 In stock
  • Manufacturer: HONEYWELL

  • Product No.: 10208/2/1

  • Condition: In stock

  • Product Type: Relay Output Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":41884368142426,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"10208\/2\/1","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Honeywell 10208\/2\/1 Relay Output Module","public_title":null,"options":["Default Title"],"price":18200,"weight":1000,"compare_at_price":39000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

The Honeywell 10208/2/1 is a 10-channel relay output module designed for the Honeywell Fail Safe Control (FSC) system. It provides potential-free relay contacts for switching external electrical loads, including resistive loads such as lamps and inductive loads such as solenoids. The module occupies 4 TE (4 HP) of rack width and 3 HE (3U) of height.

Output Function and Operating Principle

The 10208/2/1 provides ten independent relay contact output channels. Each channel uses a potential-free contact to switch an external circuit, allowing the FSC system to control field devices without directly supplying their operating power through the relay contact.

The relay outputs support resistive and inductive loads. For inductive loads, such as solenoid coils, an external suppression diode is required to limit switching transients and protect the contact circuit.

The module outputs are controlled by the system watchdog. If the system shuts down and the watchdog switches off, the relays de-energize. However, these outputs are not tested and must not be used for fail-safe applications.

Technical Specifications

Parameter Specification
Model 10208/2/1
Brand Honeywell
Product Type Relay Output Module
System Fail Safe Control (FSC)
Number of Output Channels 10
Output Specification Potential-free relay contacts
Maximum Current 2 A
Maximum Contact Voltage 30 VAC / 36 VDC
Maximum Switched Power 100 W / 1000 VA
Space Requirements 4 TE, 3 HE (4 HP, 3U)
Power Requirements 5 VDC, 25 mA; 24 VDC, 120 mA
Software Version 3.00 or later
Contact Material Gold-flush silver-cadmium oxide
Watchdog Input Current 4 mA

Rack Installation and Configuration

The 10208/2/1 requires 4 TE (4 HP) of rack width and 3 HE (3U) of height. Its rack key coding is identified by module code holes A9 and C17, with corresponding large pins A9 and C17 on the rack side.

The module supports both redundant and non-redundant I/O configurations, as documented in the Honeywell FSC hardware documentation. The applicable I/O connection arrangement and field termination hardware should be checked against the installed system configuration.

Frequently Asked Questions

Q: How many relay outputs does the Honeywell 10208/2/1 provide?

A: It provides 10 independent potential-free relay contact output channels for switching external loads.

Q: Can the 10208/2/1 be used for fail-safe output applications?

A: No. Although the relays are controlled by the system watchdog and de-energize when the watchdog switches off, the outputs are not tested and are not suitable for fail-safe applications.

Q: What precautions are required when connecting inductive loads?

A: An external suppression diode must be installed when switching inductive loads such as solenoids. The connected load must also remain within the applicable contact voltage and current ratings.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products