Description
The Honeywell CC-PCNT01 is a C300 Controller Module designed for the Experion Process Knowledge System (PKS). It functions as a distributed process controller and I/O gateway, executing configured control strategies through the Control Execution Environment (CEE) and exchanging process data with connected I/O hardware and other system nodes. The module supports Fault Tolerant Ethernet (FTE), two I/O links and controller redundancy under supported configurations.
Functional Description
The CC-PCNT01 executes control strategies within the C300 architecture. Its Control Execution Environment (CEE) processes configured control blocks and manages the exchange of process data between the controller, field I/O modules and the Experion system.
As an I/O gateway, the controller communicates with associated I/O hardware through two I/O links. This arrangement allows the controller to collect input data, execute control logic and distribute output commands through the configured I/O architecture.
Communication and I/O Architecture
The controller uses Fault Tolerant Ethernet (FTE) for communication with the Experion control network. Its two I/O links provide connections to supported Series C I/O or legacy Process Manager I/O (PMIO) configurations.
The documented standard 50 ms CEE configuration supports the following I/O link speeds:
- Series C I/O: 750 Kbaud.
- PMIO: 375 Kbaud.
The controller also supports SNTP and PTPv2 time synchronization. Peer data update periods can be configured to 100, 200, 500 or 1000 ms, depending on the application configuration.
Controller Execution and Redundancy
The standard CEE execution period is 50 ms. An optional 20 ms execution mode is also documented, requiring a separate firmware version and license. This faster mode has application restrictions and does not support the 375 Kbaud PMIO link.
Controller redundancy is supported in the standard configuration. A redundant arrangement requires two controller IOTAs and the specified redundancy connection. The controller pair must also be configured with the appropriate device indices and system settings.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | CC-PCNT01 |
| Brand | Honeywell |
| Product Type | C300 Controller Module |
| Control Platform | Experion PKS |
| Execution Environment | Control Execution Environment (CEE) |
| Control Network | Fault Tolerant Ethernet (FTE) |
| Number of I/O Links | 2 |
| Series C I/O Link Speed | 750 Kbaud |
| PMIO Link Speed | 375 Kbaud |
| Standard CEE Execution Period | 50 ms |
| Optional CEE Execution Period | 20 ms |
| Redundancy Support | Yes, subject to configuration |
| Time Synchronization | SNTP, PTPv2 |
| Peer Update Periods | 100, 200, 500, 1000 ms |
| Supply Rating | 0.311 A at 24 VDC |
| Mounting Assembly | C300 Controller IOTA |
Installation and Configuration Considerations
The CC-PCNT01 mounts on its associated Input Output Termination Assembly (IOTA), which provides the physical connection points for controller power, FTE, I/O links, redundancy and time-source connections.
When selecting a replacement or spare module, verify the following configuration details:
- Controller model and hardware revision.
- Associated IOTA and cabinet arrangement.
- Experion PKS software release and controller firmware.
- Configured CEE execution period.
- Series C I/O or PMIO link requirements.
- FTE network and controller redundancy configuration.
These checks help distinguish a physically matching controller from one that is suitable for the existing system configuration.
Frequently Asked Questions
Q: How many I/O links does the Honeywell CC-PCNT01 support?
A: The CC-PCNT01 supports two I/O links. The standard 50 ms CEE configuration supports Series C I/O at 750 Kbaud and PMIO at 375 Kbaud.
Q: Does the CC-PCNT01 support redundant controller operation?
A: Yes. It supports a redundant C300 controller arrangement using two controller IOTAs and the specified redundancy connection. The selected execution mode and system configuration must meet the applicable redundancy requirements.
Q: Can the CC-PCNT01 operate with a 20 ms CEE execution period?
A: Yes, an optional 20 ms CEE mode is documented. It requires separate firmware and licensing, has application restrictions and does not support the 375 Kbaud PMIO link.
Features
We welcome bulk orders and have a minimum order quantity of just one unit.
Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.
For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.
We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.
We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.
Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.