{"product_id":"honeywell-fc-tdol-0724p-line-monitored-digital-output-assembly","title":"Honeywell FC-TDOL-0724P Line-Monitored Digital Output Assembly","description":"\u003cp\u003eThe Honeywell FC-TDOL-0724P is a field termination assembly designed for 24 VDC line-monitored digital output circuits in the Safety Manager system. It provides seven fused relay contact outputs for non-safety-related resistive or inductive loads. Dedicated channel monitoring supports short-circuit and lead-breakage detection in both energized and de-energized states when configured with the specified Safety Manager I\/O modules and application software.\u003c\/p\u003e\n\u003ch3\u003e1. Functional Overview\u003c\/h3\u003e\n\u003cp\u003e24 VDC relay output interface\u003c\/p\u003e\n\u003cp\u003eSeven relay contact channels, each with a 2 A fuse, connect the Safety Manager output system to field loads.\u003c\/p\u003e\n\u003cp\u003eLine fault diagnostics\u003c\/p\u003e\n\u003cp\u003eIndividual monitoring circuits detect short circuits and lead breakages with the output energized or de-energized.\u003c\/p\u003e\n\u003cp\u003eDIN rail mounting and field wiring\u003c\/p\u003e\n\u003cp\u003eThe assembly supports TS32 and TS35 x 7.5 rails, with seven pairs of field screw terminals and a keyed two-pole common supply connector.\u003c\/p\u003e\n\u003ch3\u003e2. Technical Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFC-TDOL-0724P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eLine-Monitored Relay Contact Digital Output Assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem\u003c\/td\u003e\n\u003ctd\u003eSafety Manager\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e7\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Supply\u003c\/td\u003e\n\u003ctd\u003e24 VDC +\/- 20%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Output Current\u003c\/td\u003e\n\u003ctd\u003e2 A per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Field Load\u003c\/td\u003e\n\u003ctd\u003e50 W per output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Type\u003c\/td\u003e\n\u003ctd\u003eNon-safety-related resistive or inductive\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Load Resistance\u003c\/td\u003e\n\u003ctd\u003e2200 ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLeakage Current\u003c\/td\u003e\n\u003ctd\u003eApprox. 1.1 mA at 24 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOFF-State Output Voltage\u003c\/td\u003e\n\u003ctd\u003e90% of output supply voltage, as specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eON-State Output Voltage\u003c\/td\u003e\n\u003ctd\u003e100% of output supply voltage, as specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShort-Circuit Detection Threshold\u003c\/td\u003e\n\u003ctd\u003e200 ohm \u0026lt; RTh \u0026lt; 400 ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInductive Load Protection\u003c\/td\u003e\n\u003ctd\u003eSpark suppression diode specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelay Maximum Switched Power\u003c\/td\u003e\n\u003ctd\u003e150 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Relay Life\u003c\/td\u003e\n\u003ctd\u003e100,000 switching operations\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMechanical Relay Life\u003c\/td\u003e\n\u003ctd\u003e30,000,000 switching operations\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L x W x H)\u003c\/td\u003e\n\u003ctd\u003e240 x 109 x 80 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L x W x H)\u003c\/td\u003e\n\u003ctd\u003e9.45 x 4.29 x 3.15 in\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDIN Rail Length\u003c\/td\u003e\n\u003ctd\u003e241 mm (9.49 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e3. Fuse and Current Derating\u003c\/h3\u003e\n\u003cp\u003eEach output channel uses a specified 2 A fuse. The current derating curve reduces the stated current from 2 A at 25 deg C to 1.9 A at 70 deg C.\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eFuse Parameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eLittelfuse\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e0213002\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e5 x 20 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAC Voltage Rating\u003c\/td\u003e\n\u003ctd\u003e250 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDC Voltage Rating\u003c\/td\u003e\n\u003ctd\u003e300 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Current\u003c\/td\u003e\n\u003ctd\u003e2 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThe 50 W field-load limit and the 150 W maximum relay switched-power specification are separate ratings. The 150 W figure should not be interpreted as permission to exceed the stated field-load limit.\u003c\/p\u003e\n\u003ch3\u003e4. Supply and Read-Back Consumption\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eCircuit\u003c\/th\u003e\n\u003cth\u003eCurrent Consumption\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eField supply, all channels OFF\u003c\/td\u003e\n\u003ctd\u003eLess than 9 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelay and channel 8, from TSDO-0824\u003c\/td\u003e\n\u003ctd\u003eApprox. 200 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelay and channel 8, maximum at Vmax\u003c\/td\u003e\n\u003ctd\u003e250 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRead-back circuit, single SDI-1624\u003c\/td\u003e\n\u003ctd\u003eLess than 110 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRead-back circuit, redundant SDI-1624\u003c\/td\u003e\n\u003ctd\u003eLess than 210 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRead-back circuit, maximum at Vmax\u003c\/td\u003e\n\u003ctd\u003e275 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThese figures refer to different supply paths and configurations. The total system current must be determined from the actual I\/O arrangement and supply connections.\u003c\/p\u003e\n\u003ch3\u003e5. Mounting and Connection Details\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Rail\u003c\/td\u003e\n\u003ctd\u003eTS32 \/ TS35 x 7.5 DIN EN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Terminals\u003c\/td\u003e\n\u003ctd\u003e7 pairs of screw terminals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Field Wire Diameter\u003c\/td\u003e\n\u003ctd\u003e2.5 mm (AWG 14)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Wire Strip Length\u003c\/td\u003e\n\u003ctd\u003e7 mm (0.28 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Tightening Torque\u003c\/td\u003e\n\u003ctd\u003e0.5 Nm (0.37 ft-lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Supply Connector\u003c\/td\u003e\n\u003ctd\u003eKeyed two-pole header\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnector Type\u003c\/td\u003e\n\u003ctd\u003eWeidmuller BVZ 7.62HP\/02\/180F SN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnector Key\u003c\/td\u003e\n\u003ctd\u003eWeidmuller BV\/SV7.62HP KO\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Connector Strip Length\u003c\/td\u003e\n\u003ctd\u003e8 mm, as specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnectable Power Conductor Range\u003c\/td\u003e\n\u003ctd\u003e0.5-6 mm, as specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eCheck the connector keying and conductor specifications before wiring. The source data lists the power connector strip length as 8 mm but gives an inconsistent imperial conversion; verify the required preparation dimension against the applicable connector documentation.\u003c\/p\u003e\n\u003ch3\u003e6. System Configuration\u003c\/h3\u003e\n\u003cp\u003eThe line-monitoring function operates with standard Safety Manager digital input and output modules. The documented configuration references:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eSDO-0824: Associated digital output module for the specified relay and channel 8 supply path.\u003c\/li\u003e\n\u003cli\u003eSDI-1624: Digital input module used for read-back monitoring.\u003c\/li\u003e\n\u003cli\u003eApplication software: Loaded from the Safety Manager Function Library for the selected redundant or non-redundant I\/O configuration.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe assembly is intended for the documented system arrangement; line monitoring alone does not establish a safety integrity rating for connected field loads.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How many output channels does the FC-TDOL-0724P provide?\u003c\/p\u003e\n\u003cp\u003eA: It provides seven fused relay contact outputs, each rated at 2 A. The specified field-load limit is 50 W per output.\u003c\/p\u003e\n\u003cp\u003eQ: Can it detect wiring faults while the output is OFF?\u003c\/p\u003e\n\u003cp\u003eA: Yes. Its dedicated line-monitoring circuits support short-circuit and lead-breakage detection in both energized and de-energized states when used with the required Safety Manager I\/O configuration and application software.\u003c\/p\u003e\n\u003cp\u003eQ: Which DIN rails are supported?\u003c\/p\u003e\n\u003cp\u003eA: The assembly supports TS32 and TS35 x 7.5 DIN EN rails. The specified used rail length is 241 mm.\u003c\/p\u003e","brand":"HONEYWELL","offers":[{"title":"Default Title","offer_id":67784515682394,"sku":"FC-TDOL-0724P","price":159.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/FC-TDOL-0724_1.jpg?v=1792490561","url":"https:\/\/www.plcmasters.com\/products\/honeywell-fc-tdol-0724p-line-monitored-digital-output-assembly","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}