{"id":42910132600922,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"FS-TPSU-2430","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Honeywell FS-TPSU-2430 DC\/DC Converter","public_title":null,"options":["Default Title"],"price":20900,"weight":535,"compare_at_price":45000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

The Honeywell FS-TPSU-2430 is a DC/DC power converter designed for the Honeywell Safety Manager system. It converts a nominal 24 VDC input into a regulated 30 VDC output with a rated output current of 1 A. The converter supplies DC power to field termination assemblies (FTAs) that require a 30 VDC supply.

Functional Description

The FS-TPSU-2430 provides regulated DC power for connected field termination assemblies. Its 30 VDC output supports the power requirements of compatible FTA circuits, while output regulation maintains the specified voltage under changes in input voltage and load.

The 1 A output is short-circuit protected. This protection is relevant when checking field wiring and connected loads, but the total load must remain within the converter's rated output current.

Electrical Specifications

The converter accepts a nominal 24 VDC supply over an 18-36 VDC input range and produces a regulated 30 VDC output. The output tolerance is +/- 0.25 V, with less than 1% combined line and load regulation. Galvanic isolation separates the input and output circuits.

Output Monitoring and Protection

The module includes local voltage monitoring and a readback relay contact. When the 30 VDC output is within the acceptable operating condition, the status LED illuminates and the readback relay contact closes. This provides a means of monitoring the converter's output status externally.

The output has 33 V overvoltage protection, and the specified output ripple is less than 0.1 Vrms over the 0-30 MHz measurement range.

Mounting and Connections

The FS-TPSU-2430 uses a snap-in mounting provision for standard TS32 and TS35 x 7.5 DIN EN rails. It provides six pairs of output terminals for distributing 30 VDC and 0 VDC to connected FTAs.

The input and readback connections use screw terminals. The specified maximum wire size is 2.5 mm2 (AWG 14), with a 7 mm strip length and a tightening torque of 0.5 Nm.

Technical Specifications

Parameter Specification
Model FS-TPSU-2430
Brand Honeywell
Product Type DC/DC Converter
System Safety Manager
Nominal Input Voltage 24 VDC
Input Voltage Range 18-36 VDC
Maximum Inrush Current 4 A
Output Voltage 30 VDC +/- 0.25 V
Output Current 1 A
Short-Circuit Protection Yes
Short-Circuit Current Less than 3.3 A
Output Ripple Less than 0.1 Vrms (0-30 MHz)
Line and Load Regulation Less than 1%
Overvoltage Protection 33 V
Power-On Overshoot Output less than 33 V
Efficiency Greater than 75%
Switching Frequency Greater than 25 kHz
Long-Term Stability Less than 0.3% after 30 minutes
Galvanic Isolation Input to output: 2000 VAC (1 min.)
Readback Relay Contact 36 VDC / 40 mA; 30 VAC / 40 mA
Mounting TS32 / TS35 x 7.5 DIN EN rail
Dimensions 150 x 70 x 62.3 mm
Operating Temperature -5 to +70 deg C
Storage Temperature -40 to +85 deg C
Cooling Natural convection
Maximum Altitude 2000 m
Safety Class Up to and including SIL3
Approvals CE, TUV, UL, CSA, FM
MTBF Approximately 400,000 hours
Weight 1.18 lbs

Frequently Asked Questions

Q: What is the input-to-output conversion of the FS-TPSU-2430?

A: It converts a nominal 24 VDC input into an isolated 30 VDC output, rated at 1 A. The permitted input voltage range is 18-36 VDC.

Q: How can the output status be monitored?

A: The module provides a local LED and a readback relay contact. The LED illuminates and the relay contact closes when the output voltage is OK.

Q: Which DIN rail types are supported?

A: The module supports TS32 and TS35 x 7.5 DIN EN rails through its snap-in mounting provision.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products