{"product_id":"honeywell-fs-tsdi-16uni-safe-digital-input-field-termination-assembly","title":"Honeywell FS-TSDI-16UNI Safe Digital Input Field Termination Assembly","description":"\u003cp\u003eThe \u003cstrong\u003eFS-TSDI-16UNI\u003c\/strong\u003e is a 16-channel universal safe digital input Field Termination Assembly (FTA) for the Honeywell Safety Manager platform. It provides the screw-terminal interface between field devices and the system interconnection cable, supporting 24 VDC, 48 VDC and NAMUR input circuits organized in two independent groups of eight channels.\u003c\/p\u003e\n\u003ch3\u003eInput Configuration and Field Interface\u003c\/h3\u003e\n\u003cp\u003eThe module terminates sixteen discrete input loops through spring\/screw terminals and forwards the signals to the system side over an SICC-0001\/Lx cable. Each 8-channel group shares a common positive line protected by a 250 mA fuse, with a maximum sustained group output current of 175 mA. This grouping lets a field fault on one side be isolated without disabling the other eight channels.\u003c\/p\u003e\n\u003ch3\u003eSystem Connection\u003c\/h3\u003e\n\u003cp\u003eThe FTA is a passive termination device and does not process logic by itself. It connects to one or a redundant pair of SDIL-1608 safe digital input modules through the SICC interconnection cable. Correct operation depends on the FTA, cable and SDIL-1608 being commissioned together as a single signal path; channel diagnostics and line monitoring are evaluated on the module side.\u003c\/p\u003e\n\u003ch3\u003eConstruction and Mounting\u003c\/h3\u003e\n\u003cp\u003eThe \"FS\" prefix denotes the non-conformal-coated version intended for standard cabinet environments; FC-TSDI-16UNI is the conformal-coated equivalent. The unit snaps onto standard DIN EN rails (TS32\/TS35) and uses 2.5 mm² (AWG 14) max field conductors with a recommended terminal torque of 0.5 Nm.\u003c\/p\u003e\n\u003ch3\u003eTechnical Data\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFS-TSDI-16UNI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eSafe Digital Input FTA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 (2 groups of 8)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Signals\u003c\/td\u003e\n\u003ctd\u003e24 VDC, 48 VDC, DIN NAMUR\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGroup Protection\u003c\/td\u003e\n\u003ctd\u003e250 mA fuse in common positive line\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax Group Output\u003c\/td\u003e\n\u003ctd\u003e175 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Interface\u003c\/td\u003e\n\u003ctd\u003eSICC-0001\/Lx cable to SDIL-1608 (redundant pair supported)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Wiring\u003c\/td\u003e\n\u003ctd\u003eScrew terminal, max 2.5 mm² \/ AWG 14\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eDIN EN rail snap-in (TS32\/TS35)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Torque\u003c\/td\u003e\n\u003ctd\u003e0.5 Nm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Rating\u003c\/td\u003e\n\u003ctd\u003eUp to 150 VDC (per IEC 61010-1, dep. on connected module)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eNon-conformal (FS); FC variant conformal-coated\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.14 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e90 x 70 x 60 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the FS-TSDI-16UNI work alone as a digital input module?\u003c\/p\u003e\n\u003cp\u003eA: No. It is a field termination assembly. It must be linked via the SICC cable to an SDIL-1608 (or redundant SDIL-1608 pair) to read field states.\u003c\/p\u003e\n\u003cp\u003eQ: What is the difference between FS-TSDI-16UNI and FC-TSDI-16UNI?\u003c\/p\u003e\n\u003cp\u003eA: Same electrical function; FS is non-conformal coated for standard cabinets, FC adds conformal coating for humid or corrosive environments.\u003c\/p\u003e\n\u003cp\u003eQ: Can 24 VDC and NAMUR sensors share the same group?\u003c\/p\u003e\n\u003cp\u003eA: Field voltage and sensor type must match the approved group configuration. Mixing incompatible circuit types on one fused group is not recommended without verifying the SDIL-1608 settings.\u003c\/p\u003e","brand":"HONEYWELL","offers":[{"title":"Default Title","offer_id":42561308098650,"sku":"FS-TSDI-16UNI","price":209.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/FS-TSDI-16UNI2.jpg?v=1763106184","url":"https:\/\/www.plcmasters.com\/products\/honeywell-fs-tsdi-16uni-safe-digital-input-field-termination-assembly","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}