Honeywell FS-TSDO-04UNI Safety Digital Output FTA

Honeywell FS-TSDO-04UNI Safety Digital Output FTA

  • 1000 In stock
  • Manufacturer: HONEYWELL

  • Product No.: FS-TSDO-04UNI

  • Condition: In stock

  • Product Type: Safety Digital Output FTA

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 400g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":42912751943770,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"FS-TSDO-04UNI","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Honeywell FS-TSDO-04UNI Safety Digital Output FTA","public_title":null,"options":["Default Title"],"price":20900,"weight":400,"compare_at_price":45000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

The FS-TSDO-04UNI is a four-channel safe digital output field termination assembly (FTA) for Honeywell Safety Manager and FSC architectures. It bridges the system interconnection cable to external field wiring through screw terminals, supporting line monitoring and redundant output pairing. The module provides isolated termination rather than signal generation, relying on the connected safety output module for drive logic.

Function and System Role

The FTA receives de-energize-to-trip output states from Safety Manager SDO-04x / SDOL-04x modules or FSC 10213/2/x and 10216/2/x output modules. Each channel can be configured as a single output or as a redundant pair, allowing the safety logic solver to detect short circuits, broken wires, and stuck-on conditions before they affect the final element.

Field Wiring and Mechanical Configuration

Field connections use screw terminals rated for wires up to 2.5 mm² (AWG 14), with a strip length of approximately 7 mm and a tightening torque of 0.5 Nm. The unit mounts on a standard TS32 DIN rail (EN 50022 / 35 mm rail compatible footprint referenced in the original data sheet) and occupies about 61 mm of rail length. No internal power conversion is performed; the continuous channel current is defined by the connected output module.

Electrical Ratings and Approvals

The termination side is rated for field voltages up to 50 VDC under IEC 1010 overvoltage category II, and up to 150 VDC under overvoltage category I conditions. Approvals cited for the series include CE, TÜV, UL, CSA, and FM, although specific FM scope should be confirmed against the current certificate for the ordered variant.

Variant Identification

FS-prefixed units are standard non-conformal-coated assemblies; FC-prefixed units carry conformal coating. Conformal-coated revisions may show “CC” ahead of the version number. When verifying spares, match both the prefix and the mechanical revision, not only the TSDO-04UNI base designation.

Parameter Specification
Model FS-TSDO-04UNI
Brand Honeywell
Product Type Safety digital output FTA (field termination assembly)
Channels 4
Compatible Logic Outputs Safety Manager SDO-04x, SDOL-04x; FSC 10213/2/x, 10216/2/x
Field Voltage Rating 50 VDC (IEC 1010 cat. II); 150 VDC (cat. I)
Max Continuous Current Defined by connected output module
Termination Screw terminals, 2.5 mm² / AWG 14 max
Strip Length 7 mm
Tightening Torque 0.5 Nm
Mounting TS32 DIN rail, 61 mm rail length
Diagnostics Line monitoring: open wire, short circuit, feedback comparison
Coating Option FS = non-conformal; FC = conformal coated
Approvals CE, TÜV, UL, CSA, FM (verify per variant)

Frequently Asked Questions

Q: Does the FS-TSDO-04UNI generate the 24 VDC output itself?

A: No. It is a termination and line-monitoring interface. The actual safety output drive comes from the paired SDO/SDOL or FSC output module.

Q: Can it be used with both Safety Manager and older FSC systems?

A: Yes, provided the correct output module is installed: SDO-04x/SDOL-04x for Safety Manager, or 10213/2/x and 10216/2/x for FSC.

Q: What is the difference between FS-TSDO-04UNI and FC-TSDO-04UNI?

A: The FS version is non-conformal-coated; the FC version is conformal-coated for harsher environments. Electrical function is otherwise equivalent.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products