{"product_id":"honeywell-fs-tsdo-04uni-safety-digital-output-fta","title":"Honeywell FS-TSDO-04UNI Safety Digital Output FTA","description":"\u003cp\u003eThe \u003cstrong\u003eFS-TSDO-04UNI\u003c\/strong\u003e is a four-channel safe digital output field termination assembly (FTA) for Honeywell Safety Manager and FSC architectures. It bridges the system interconnection cable to external field wiring through screw terminals, supporting line monitoring and redundant output pairing. The module provides isolated termination rather than signal generation, relying on the connected safety output module for drive logic.\u003c\/p\u003e\n\u003ch3\u003eFunction and System Role\u003c\/h3\u003e\n\u003cp\u003eThe FTA receives de-energize-to-trip output states from Safety Manager SDO-04x \/ SDOL-04x modules or FSC 10213\/2\/x and 10216\/2\/x output modules. Each channel can be configured as a single output or as a redundant pair, allowing the safety logic solver to detect short circuits, broken wires, and stuck-on conditions before they affect the final element.\u003c\/p\u003e\n\u003ch3\u003eField Wiring and Mechanical Configuration\u003c\/h3\u003e\n\u003cp\u003eField connections use screw terminals rated for wires up to 2.5 mm² (AWG 14), with a strip length of approximately 7 mm and a tightening torque of 0.5 Nm. The unit mounts on a standard TS32 DIN rail (EN 50022 \/ 35 mm rail compatible footprint referenced in the original data sheet) and occupies about 61 mm of rail length. No internal power conversion is performed; the continuous channel current is defined by the connected output module.\u003c\/p\u003e\n\u003ch3\u003eElectrical Ratings and Approvals\u003c\/h3\u003e\n\u003cp\u003eThe termination side is rated for field voltages up to 50 VDC under IEC 1010 overvoltage category II, and up to 150 VDC under overvoltage category I conditions. Approvals cited for the series include CE, TÜV, UL, CSA, and FM, although specific FM scope should be confirmed against the current certificate for the ordered variant.\u003c\/p\u003e\n\u003ch3\u003eVariant Identification\u003c\/h3\u003e\n\u003cp\u003eFS-prefixed units are standard non-conformal-coated assemblies; FC-prefixed units carry conformal coating. Conformal-coated revisions may show “CC” ahead of the version number. When verifying spares, match both the prefix and the mechanical revision, not only the TSDO-04UNI base designation.\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFS-TSDO-04UNI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eSafety digital output FTA (field termination assembly)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannels\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible Logic Outputs\u003c\/td\u003e\n\u003ctd\u003eSafety Manager SDO-04x, SDOL-04x; FSC 10213\/2\/x, 10216\/2\/x\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Voltage Rating\u003c\/td\u003e\n\u003ctd\u003e50 VDC (IEC 1010 cat. II); 150 VDC (cat. I)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax Continuous Current\u003c\/td\u003e\n\u003ctd\u003eDefined by connected output module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTermination\u003c\/td\u003e\n\u003ctd\u003eScrew terminals, 2.5 mm² \/ AWG 14 max\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStrip Length\u003c\/td\u003e\n\u003ctd\u003e7 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTightening Torque\u003c\/td\u003e\n\u003ctd\u003e0.5 Nm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eTS32 DIN rail, 61 mm rail length\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostics\u003c\/td\u003e\n\u003ctd\u003eLine monitoring: open wire, short circuit, feedback comparison\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating Option\u003c\/td\u003e\n\u003ctd\u003eFS = non-conformal; FC = conformal coated\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCE, TÜV, UL, CSA, FM (verify per variant)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the FS-TSDO-04UNI generate the 24 VDC output itself?\u003c\/p\u003e\n\u003cp\u003eA: No. It is a termination and line-monitoring interface. The actual safety output drive comes from the paired SDO\/SDOL or FSC output module.\u003c\/p\u003e\n\u003cp\u003eQ: Can it be used with both Safety Manager and older FSC systems?\u003c\/p\u003e\n\u003cp\u003eA: Yes, provided the correct output module is installed: SDO-04x\/SDOL-04x for Safety Manager, or 10213\/2\/x and 10216\/2\/x for FSC.\u003c\/p\u003e\n\u003cp\u003eQ: What is the difference between FS-TSDO-04UNI and FC-TSDO-04UNI?\u003c\/p\u003e\n\u003cp\u003eA: The FS version is non-conformal-coated; the FC version is conformal-coated for harsher environments. Electrical function is otherwise equivalent.\u003c\/p\u003e","brand":"HONEYWELL","offers":[{"title":"Default Title","offer_id":42912751943770,"sku":"FS-TSDO-04UNI","price":209.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/FS-TSDO-04UNI2.jpg?v=1770795243","url":"https:\/\/www.plcmasters.com\/products\/honeywell-fs-tsdo-04uni-safety-digital-output-fta","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}