Skip to content
Honeywell FS-TSGAS-1624 Fail-Safe Gas-Flame Detector Input FTA

Honeywell FS-TSGAS-1624 Fail-Safe Gas-Flame Detector Input FTA

  • 18 In stock
  • Manufacturer: HoneyWell

  • Product No.: FS-TSGAS-1624

  • Condition: In stock

  • Product Type: Fail-Safe Gas-Flame Detector Input FTA

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":68091791671386,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"FS-TSGAS-1624","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Honeywell FS-TSGAS-1624 Fail-Safe Gas-Flame Detector Input FTA","public_title":null,"options":["Default Title"],"price":22000,"weight":1000,"compare_at_price":51000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

The Honeywell FS-TSGAS-1624 is a Fail-Safe Gas-Flame Detector Input Field Termination Assembly (FTA) designed to interface 16 analog current-input channels with an SAI-1620m module. It accepts 0-20 mA field signals through 500 ohm input resistance and provides corresponding 0-4 VDC outputs with 0.1% accuracy.

Input Channel Configuration

The FS-TSGAS-1624 provides 16 analog input channels, each designed for a 0-20 mA current signal. All channels use a common 0 V reference.

The 500 ohm input resistance establishes the current-to-voltage conversion relationship. At the 0-20 mA input range, the nominal voltage across this resistance is 0-10 V before the assembly's signal conditioning and output stage.

Signal Interface

The FTA provides 0-4 VDC outputs to the SAI-1620m module, with a specified accuracy of 0.1%. This voltage interface allows the receiving module to acquire the conditioned field-input signals.

The external 24 VDC supply powers the assembly. Its stated current draw is 3 mA without field loads, so this figure should not be treated as the total operating current when external field devices are connected.

Technical Specifications

Parameter Specification
Model FS-TSGAS-1624
Brand Honeywell
Product Type Fail-Safe Gas-Flame Detector Input FTA
Input Channels 16 analog channels
Nominal Input Signal 0-20 mA
Input Current Range 0-25 mA
Input Reference Common 0 V
Input Resistance 500 ohm +/-5%
Output Voltage 0-4 VDC
Output Interface SAI-1620m
Output Accuracy 0.1%
External Power Supply 24 VDC
Current Consumption 3 mA without field loads
Fuse Rating 500 mA, slow-acting
Fuse Dimensions 5 x 20 mm
Fuse AC Voltage Rating 250 V
Fuse DC Voltage Rating 300 V
Mounting Rail TS32 / TS35 x 7.5 DIN EN rail
Used Rail Length 226 mm
Module Dimensions 225 x 70 x 60 mm (L x W x H)
Approvals CE, TUV, UL, CSA, FM

Field Wiring and Protection

The assembly provides field termination for 16 analog signal channels. Its screw-terminal arrangement supports connections for field signals, power supply and grounding. The hardware reference also specifies a 500 mA slow-acting fuse rated for 250 VAC or 300 VDC, with a 5 x 20 mm fuse format.

The specified mounting options are TS32 and TS35 x 7.5 DIN EN rails. The required rail length is 226 mm, which should be considered when checking cabinet space and replacement arrangements.

Frequently Asked Questions

Q: Which analog input module receives signals from the FS-TSGAS-1624?

A: The specified receiving module is the Honeywell SAI-1620m. The FTA conditions the field input signals and provides 0-4 VDC outputs to this module.

Q: Does the FS-TSGAS-1624 support 4-20 mA field signals?

A: Its documented nominal signal designation is 0-20 mA, while the hardware reference specifies an electrical input range of 0-25 mA. Confirm the detector signal configuration and system engineering requirements before using a particular signal range.

Q: What should be checked when replacing this FTA?

A: Verify the complete FS-TSGAS-1624 part number, 16-channel wiring arrangement, common 0 V reference, external 24 VDC supply, fuse specification and SAI-1620m interface. Also check the DIN rail dimensions and field terminal assignments before installation.

Sources and Configuration Notes

The specifications are cross-checked against Honeywell's Safety Manager Hardware Reference, Release 162, Issue 2.1, December 2023, Section 15.28, TSGAS-1624.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured