Description
The Honeywell FX-USI-0002 is identified as a Safety Manager System Module for Honeywell safety control systems. The supplied product information confirms the manufacturer and part number but does not specify its channel configuration, electrical characteristics, communication interfaces, or functional safety ratings.
Functional Description
The FX-USI-0002 is a Universal Safety Interface (USI) communication module installed in the Honeywell Safety Manager controller chassis. It manages Ethernet and serial communications between the Safety Manager controller and external devices, including Experion PKS and Safety Builder.
The module also provides a hardware firewall function to protect Safety Manager safety functions during external communication. Its communication resources support data exchange with other Safety Managers and connected supervisory systems.
Communication Interfaces
The module provides four independent communication channels, identified as A, B, C, and D.
- Channel A: 10/100 Mbps Ethernet interface with an RJ45 connector. It connects to the SDW-550-EC through CCI-HSE-01 or CCI-HSE-02 cables.
- Channel C: General-purpose serial communication interface with a 10-pin AMP connector. It connects to DCOM-232/485 or DCOM-485 through CCI-UNI-02 or CCI-UNI-04 cables.
- Channels B and D: Additional communication channels identified in the hardware reference. Their specific interface assignments are not detailed in the cited channel table.
The Ethernet interfaces automatically select between 10 Mbps and 100 Mbps. Honeywell recommends configuring the Ethernet port for fixed 100 Mbps, full-duplex operation.
Hardware Architecture and Diagnostics
The FX-USI-0002 incorporates dedicated communication processing and memory resources for handling multiple communication protocols.
Its hardware architecture includes:
- Motorola 8270 communication processor.
- 8 MB Flash memory for system and application programs.
- 8 MB local SRAM with error detection and correction logic.
- 256 KB shared RAM for data exchange with the Control Processor.
- Two dual-speed Ethernet transceivers.
- Two general-purpose serial communication controller channels.
The module performs power-up self-tests covering processor registers, local and shared memory, exception handling, and software integrity. A dedicated watchdog monitors communication processing and resets communication channels if a watchdog timeout occurs.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | FX-USI-0002 |
| Brand | Honeywell |
| Product Type | Universal Safety Interface Module |
| System Platform | Safety Manager |
| Communication Channels | 4 independent channels |
| Ethernet | 10/100 Mbps |
| Ethernet Connector | RJ45 |
| Serial Interface | General-purpose serial |
| Serial Connector | 10-pin AMP |
| Supported Protocol | EUCN |
| Flash Memory | 8 MB |
| Local SRAM | 8 MB with error detection and correction |
| Shared RAM | 256 KB |
| Ethernet Transceivers | 2 |
| Serial Communication Controllers | 2 |
| Supply Voltage | 5 V DC +/- 5% |
| Maximum Supply Current | 1.2 A |
| Operating Temperature | -5 to +70 deg C |
| Storage Temperature | -40 to +85 deg C |
| Relative Humidity | 10-95%, non-condensing |
| Galvanic Isolation | >= 2.5 kV DC between 5 V DC and Ethernet signal |
| Ethernet-to-Casing Isolation | >= 1.5 kV DC |
| Supply-to-Casing Isolation | >= 1.5 kV DC |
| Approvals | CE, TUV, UL, CSA, FM |
| Dimensions (H x W x D) | 176 x 35.2 x 212 mm |
| Weight | 0.7 kg |
System Compatibility and Replacement
The FX-USI-0002 is documented as a replacement for the following earlier Universal Safety Interface modules:
- FC-USI-0001
- FC-USI-0002
- FE-USI-0002
Honeywell specifies that the FX-USI-0002 supports replacement from Safety Manager software release R140 and higher. The replacement relationship is relevant when maintaining existing controller installations, but the installed software release should be checked before ordering or replacing the module.
The FX-USI-0002 also supports the EUCN protocol, which is relevant when checking communication compatibility with existing Safety Manager configurations.
Installation and Maintenance Considerations
The module is installed in the Safety Manager Controller chassis and occupies a communication module position.
Honeywell documents hot-swap functionality: the module can be inserted or removed while the system is running without interrupting the application program.
Before replacement, verify the controller software release, communication configuration, cable connections, and channel assignments.
Frequently Asked Questions
Q: Can the FX-USI-0002 replace the older FE-USI-0002 module?
A: Yes. Honeywell identifies the FX-USI-0002 as a replacement for FE-USI-0002, FC-USI-0001, and FC-USI-0002. The Safety Manager software must meet the R140 or higher compatibility requirement.
Q: Does the FX-USI-0002 support hot swapping?
A: Yes. The module supports insertion and removal in a running Safety Manager system without interrupting the application program.
Q: What communication interfaces are available on the FX-USI-0002?
A: The module provides four independent communication channels, including a 10/100 Mbps Ethernet interface and a general-purpose serial interface. The exact cable and external interface requirements depend on the selected channel and system configuration.
Features
We welcome bulk orders and have a minimum order quantity of just one unit.
Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.
For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.
We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.
We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.
Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.