{"product_id":"honeywell-tk-ccr013-redundant-controlnet-interface-module","title":"Honeywell TK-CCR013 Redundant ControlNet Interface Module","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell TK-CCR013\u003c\/strong\u003e is a dual-media redundant ControlNet interface module designed for Honeywell Experion PKS control system architectures. It provides a communication path between the controller chassis and the ControlNet network using separate A and B media connections. The TK prefix identifies the coated version of the module, distinguishing it from the corresponding non-coated TC model.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eControlNet Communication Architecture\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module supports dual-media ControlNet communication. The A and B network connections provide separate communication paths, allowing the system to use a redundant media configuration rather than relying on a single network cable.\u003c\/p\u003e\n\u003cp\u003eWithin an Experion PKS architecture, the ControlNet Interface (CNI) provides communication between the server, C200 controllers, and associated I\/O modules. The network configuration and module placement must follow the controller chassis design.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eHardware Identification and Lifecycle\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eHoneywell documentation identifies the TK-CCR013 as a \u003cstrong\u003eSeries D, obsolete dual-media redundant ControlNet interface\u003c\/strong\u003e. The TK prefix denotes the coated version of the ControlNet module.\u003c\/p\u003e\n\u003cp\u003eThe Series E CCR014 family supersedes the Series D CCR013 models. This is an important consideration when maintaining older redundant controller chassis.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eTK-CCR013\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eRedundant ControlNet Interface Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Platform\u003c\/td\u003e\n\u003ctd\u003eExperion PKS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork Type\u003c\/td\u003e\n\u003ctd\u003eControlNet\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork Configuration\u003c\/td\u003e\n\u003ctd\u003eDual-Media \/ Redundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Series\u003c\/td\u003e\n\u003ctd\u003eSeries D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eCoated version\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLifecycle Status\u003c\/td\u003e\n\u003ctd\u003eObsolete\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSuccessor Series\u003c\/td\u003e\n\u003ctd\u003eSeries E CCR014\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eNetwork Connections and Replacement Considerations\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eA and B connections:\u003c\/strong\u003e The two network connections support the dual-media ControlNet configuration. Corresponding network drop cables must be connected to their designated module connectors.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSingle-media operation:\u003c\/strong\u003e A dual-media module can also be used in a single-media network configuration, with the network drop cable connected to port A.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRedundant chassis replacement:\u003c\/strong\u003e Honeywell specifies replacing both partner CCN012\/CCR012 or CCN013\/CCR013 modules with the corresponding Series E CCN014\/CCR014 modules when a legacy module fails in a redundant chassis pair. Both partner modules must be the same type.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCommissioning checks:\u003c\/strong\u003e Verify the replacement firmware and confirm that the module passes its power-up diagnostics. ControlNet parameters, including keeper values, should also be checked after communication is established.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between TK-CCR013 and TC-CCR013?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Both are Series D dual-media redundant ControlNet interface models. The TK prefix identifies the coated version, while the TC model is the corresponding standard version.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can TK-CCR013 be directly replaced with TK-CCR014?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: TK-CCR014 belongs to the successor Series E family. For a redundant chassis pair, Honeywell requires both partner modules to be replaced with matching Series E module types. Firmware and system configuration must also be checked before returning the controller to operation.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can TK-CCR013 operate with only one ControlNet cable?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. The dual-media interface can operate in a single-media configuration using port A. For redundant media operation, use the designated A and B connections.\u003c\/p\u003e","brand":"HoneyWell","offers":[{"title":"Default Title","offer_id":68111484747866,"sku":"TK-CCR013","price":220.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/TK-CCR0132.jpg?v=1794904029","url":"https:\/\/www.plcmasters.com\/products\/honeywell-tk-ccr013-redundant-controlnet-interface-module","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}