{"product_id":"honeywell-tk-hai081-hart-analog-input-module","title":"Honeywell TK-HAI081 HART Analog Input Module","description":"\u003cp\u003eConfigured for multi-channel analog signal acquisition in compatible Honeywell control architectures, the Honeywell TK-HAI081 (TK-HAI081) HART Analog Input Module provides 8 input channels for 4-20 mA DC, 0-20 mA, and +\/-20 V signals. It supports HART communication pass-through to Experion PKS and provides channel-to-channel and channel-to-bus galvanic isolation. The module is identified as CIOM-A with conformal coating.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eThe supplied information identifies TK-HAI081 as the complete model number and CIOM-A as its module designation. No additional ordering-code suffix breakdown is provided.\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eTK-HAI081\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Designation\u003c\/td\u003e\n\u003ctd\u003eCIOM-A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003eHART Analog Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Count\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signal Range\u003c\/td\u003e\n\u003ctd\u003e4-20 mA DC, 0-20 mA, +\/-20 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHART Communication\u003c\/td\u003e\n\u003ctd\u003ePass-through to Experion PKS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Resolution\u003c\/td\u003e\n\u003ctd\u003e12-16 bit; typically 12-bit effective\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003e+\/-0.15% of full scale at 25 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eExperion PKS (C300 Controller \/ C200 \/ ControlLogix platform, as specified)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.5 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e216 x 160 x 30 mm (H x W x D)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e2.5 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Loop Update Time\u003c\/td\u003e\n\u003ctd\u003eLess than 250 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003eChannel-to-channel and channel-to-bus galvanic isolation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eConformal coating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eAnalog Input Processing and HART Pass-Through\u003c\/h3\u003e\n\u003cp\u003eThe TK-HAI081 converts field analog signals into digital values for use by the host control system. Its specified input ranges include current and voltage signals. The stated A\/D resolution is 12-16 bit, with 12-bit effective resolution typically indicated in the supplied data.\u003c\/p\u003e\n\u003cp\u003eHART pass-through supports communication between compatible HART field instruments and Experion PKS. Actual communication behavior depends on the field device, loop configuration, and host interface.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: What is the analog input update time?\u003c\/p\u003e\n\u003cp\u003eA: The supplied specification lists an analog loop update time of less than 250 ms.\u003c\/p\u003e\n\u003cp\u003eQ: What isolation does the TK-HAI081 provide?\u003c\/p\u003e\n\u003cp\u003eA: Channel-to-channel and channel-to-bus galvanic isolation are specified. Detailed isolation voltage ratings are not provided.\u003c\/p\u003e\n\u003cp\u003eQ: Is hot-swap operation supported?\u003c\/p\u003e\n\u003cp\u003eA: Hot-swap capability is not confirmed by the supplied data. Check the applicable host platform and module installation documentation before removal or insertion under power.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eConfirm the module identity and terminal assignments against the applicable installation manual.\u003c\/li\u003e\n\u003cli\u003eMatch each field signal type to the configured input range before connecting the loop.\u003c\/li\u003e\n\u003cli\u003eCheck signal polarity, loop power requirements, and field-device wiring.\u003c\/li\u003e\n\u003cli\u003eSeparate low-level analog wiring from high-voltage and switching circuits.\u003c\/li\u003e\n\u003cli\u003eGround cable shields according to the control system grounding design.\u003c\/li\u003e\n\u003cli\u003eVerify module temperature and humidity conditions against the listed limits.\u003c\/li\u003e\n\u003cli\u003eConfirm HART communication at the host system after wiring and configuration.\u003c\/li\u003e\n\u003cli\u003eDo not assume hot-swap capability or an isolation voltage rating without manufacturer documentation.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"HoneyWell","offers":[{"title":"Default Title","offer_id":41914563199066,"sku":"TK-HAI081","price":176.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0612\/4601\/3530\/files\/TK-HAI0812.jpg?v=1792381995","url":"https:\/\/www.plcmasters.com\/products\/honeywell-tk-hai081-hart-analog-input-module","provider":"PLC Masters Ltd.","version":"1.0","type":"link"}