{"id":44010663706714,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"T3488","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ICS Triplex T3488 Regent Guarded Digital Output Module","public_title":null,"options":["Default Title"],"price":12300,"weight":1800,"compare_at_price":32000,"inventory_management":"shopify","barcode":null,"requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

The ICS Triplex T3488, also cataloged as the T3488 Guarded Digital Output Module, operates as a dedicated hardware component for switching high-voltage DC safety loads within Regent T3xxx Safetybus platforms.

Hardware Specifications

Parameter Specification
Model T3488
Brand ICS Triplex
Origin United Kingdom
Weight 1.80 kg
Dimensions Standard Regent Module Size
Operating Temp 0 to 60 deg C
Power Consumption 15 W (Logic Side)
Channel Capacity 16 monitored outputs (2 isolated groups of 8)
Nominal Voltage 125 VDC (100 to 140 VDC operating range)
Load Current Up to 2 A per channel
Architecture Guarded dual-redundant logic with voter circuits
Isolation 2500 V optical/galvanic barrier
Certification IEC 61508 SIL 3, TUV Certified, Risk Class 5
Diagnostics Continuous open-circuit, short-circuit, and fuse monitoring

SIL3 Safety & Triple Modular Redundancy

The module incorporates a guarded dual-redundant logic architecture tied directly to the triplicated Regent I/O Safetybus interface, achieving fully deterministic fault-tolerant execution. Integrated voting circuits enforce a fail-safe state execution, preventing any single hardware fault from inadvertently energizing connected field devices. Complete 2500 V optical and galvanic isolation between field-side wiring and internal logic processing prevents transient electrical spikes from compromising system integrity. Continuous real-time diagnostic routines execute line monitoring to detect open-circuit and short-circuit faults instantly, validating output health and fuse continuity without disrupting active safety loops.

Frequently Asked Questions

Q: Can the T3488 module be hot-swapped during active system operation without disrupting safety loops?

A: Yes, the T3488 supports full hot-replacement capability. Maintenance personnel can extract and install the module under power without interrupting the triplicated Safetybus or shutting down active SIL 3 safety functions.

Q: What mechanisms protect the field outputs against overcurrent and wiring integrity failures?

A: Each output channel features continuous line monitoring for open and short circuits, coupled with individual front-panel accessible fuses to isolate overcurrent conditions per line.

Field Installation Guidelines

Ensure the module chassis is grounded via a low-impedance copper strap to the main cabinet protective earth (PE) before slot insertion. Field wiring for the 125 VDC channels must maintain separation from low-voltage signaling cables to prevent capacitive noise coupling. All shield terminations for field cabling should be grounded at a single point, typically the cabinet entry gland plate, to eliminate ground loop currents. Verify that field power supplies do not exceed the 140 VDC upper threshold under maximum load step conditions. Standard 35 mm DIN-rail or rack mounting structures must provide adequate clearance to ensure vertical airflow across the chassis heat dissipators.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products