Skip to content
ICS Triplex T7481 Regent+Plus Monitored Guarded Output Module

ICS Triplex T7481 Regent+Plus Monitored Guarded Output Module

  • 16 In stock
  • Manufacturer: ICS Triplex

  • Product No.: T7481

  • Condition: In stock

  • Product Type: Regent+Plus Monitored Guarded Output Module

  • Payment:T/T, Western Union

  • Weight: 1800g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":44023965810778,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"T7481","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ICS Triplex T7481 Regent+Plus Monitored Guarded Output Module","public_title":null,"options":["Default Title"],"price":12300,"weight":1800,"compare_at_price":32000,"inventory_management":"shopify","barcode":null,"requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Configured for high-integrity load execution in Regent+Plus Safetybus platforms, the ICS Triplex T7481 (T7481 Monitored Guarded Output Module) provides direct physical/electrical execution.

Suffix Breakdown & Model Matrix

Base Model Suffix / Configuration Module Architecture Output Voltage Channel Count
T7481 Standard Assembly Dual-Redundant Guarded 24 VDC 16 Channels (2 groups of 8)

Hardware Specifications

Parameter Specification
Model T7481
Brand ICS Triplex
Origin United Kingdom
Weight 1.8 kg
Dimensions 30.5 cm x 4.2 cm x 28.0 cm
Operating Temp 0 to 60 deg C
Power Consumption 15 W (logic side)
Output Rating 24 VDC solid-state, 2 A continuous per channel (0 to 40 deg C)
Voltage Range 18 to 36 VDC
Isolation 2500 V between field and logic circuits
Minimum Load 20 mA (5 mA typical)
On-State Voltage Drop <= 1.0 V
Surge Current Limit 3.5 A peak, 7 A for 20 ms
Leakage Current <= 5 mA (single fault), <= 7.5 mA (dual fault)
Protection 3 A fast-acting front-mounted fuse per channel

Triple Modular Redundancy (TMR) & SIL3 Execution

The unit integrates directly with a triplicated Safetybus backplane interface to achieve strict fault isolation and high availability. Designed for SIL3 and TÜV Risk Class 5 critical loops, the hardware features a dual-redundant guarded output circuit topology. This design guarantees that no single component failure or spurious control signal can inadvertently energize an attached field load, such as a emergency shutdown valve or turbine trip solenoid. The module continuously executes automatic line monitoring, measuring field wiring conditions for open-circuit and short-circuit faults while maintaining channel-to-channel galvanic isolation up to 2500 V.

Frequently Asked Questions

Q: Can the T7481 module be hot-swapped during active system operation without tripping the process?

A: Yes. The module features complete hot-replace capability. It can be removed and inserted into an active Regent+Plus chassis without disrupting power to adjacent modules or triggering a system-level fail-safe shutdown.

Q: How does the internal line monitoring respond to a blown channel fuse?

A: Each output channel incorporates a front-mounted 3 A fast-acting fuse. If a fuse opens or a field load drops below 20 mA, the internal diagnostic circuit immediately flags a fault condition, illuminates the corresponding front panel LED indicator, and transmits the diagnostic status over the Safetybus.

Field Installation Guidelines

  • Chassis Mounting: Seat the module firmly into the designated slot of the Regent+Plus chassis, ensuring top and bottom retaining screws are fully torqued to maintain ground continuity across the backplane.
  • Wiring & Shielding: Connect all 24 VDC field wiring to the appropriate field termination assembly. Maintain strict separation between field output lines and high-voltage AC cables. Ground all cable shields at a single point on the chassis earth bus.
  • Fuse Inspection: Verify that each of the 16 front-accessible 3 A fast-acting fuses is intact prior to energizing the load power supply.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.