Skip to content
ICS Triplex T8293 Trusted 15-Way Fused DC Power Distribution Unit

ICS Triplex T8293 Trusted 15-Way Fused DC Power Distribution Unit

  • 16 In stock
  • Manufacturer: ICS Triplex

  • Product No.: T8293

  • Condition: In stock

  • Product Type: Trusted 15-Way Fused DC Power Distribution Unit

  • Payment:T/T, Western Union

  • Weight: 576g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":44028616540250,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"T8293","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ICS Triplex T8293 Trusted 15-Way Fused DC Power Distribution Unit","public_title":null,"options":["Default Title"],"price":12300,"weight":576,"compare_at_price":32000,"inventory_management":"shopify","barcode":null,"requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Configured for high-integrity field power distribution in SIL3 safety instrumented systems, the ICS Triplex T8293 (T8293 DC Power Distribution Unit) provides direct physical/electrical execution. It handles field termination assembly feeding, solenoid activation, and sensor loops through dual-redundant power rails with high channel isolation.

Hardware Specifications

Parameter Specification
Model T8293
Brand ICS Triplex
Origin United Kingdom
Weight 576 g
Dimensions 79 x 285 x 109 mm
Operating Temp -5 to +60 deg C (Standard T8293) / -40 to +70 deg C (Coated T8293C)
Power Consumption Passive distribution board; loss limited to internally fused paths
Input Voltage Range Link-selectable 24 VDC (22-30 VDC) or 48 VDC (43-60 VDC)
Maximum Input Current 23 A total
Output Distribution 15 dual fused outputs, 3.15 A max per channel
Protection Fuse Standard IEC 60269-1 fast-acting or slow-blow cartridge fuses
Galvanic Isolation 1000-1500 VDC input-to-output
Diagnostic Fault Relay Dry contact (NC/NO configurable) for fuse blow indication
Mounting Type EN 50022 35 mm DIN-rail
Relative Humidity 5%-95% non-condensing

Triple Modular Redundancy & Safety Features

Designed for inclusion within Trusted TMR architecture, the unit executes fail-safe state execution through dedicated fault isolation pathways. Each of the 15 output channels features independent fusing to prevent single-channel short circuits from corrupting main system power buses. Redundant dual-input paths ensure seamless power source transfer without interrupting power delivery to critical safety logic cards, controllers, or actuators. Signal paths utilize 1000-1500 VDC galvanic isolation to stop ground potential shifts from spreading to core logic racks.

Frequently Asked Questions

Q: Can fuses be replaced while the T8293 unit remains energized during active system execution?A: Yes. Individual channel cartridge fuses allow hot-swap maintenance under power, provided local hazardous location zone classification requirements and tool isolation procedures are followed.

Q: How does the dry contact alarm output function when an output fuse open-circuit condition occurs?A: The alarm output uses an onboard monitoring loop that senses voltage drops across each fuse path. When any of the 15 fuses opens, the configurable NC/NO dry contact changes state to trigger diagnostic alerts on the central system controller.

Q: Is the T8293 compatible with both 24 VDC and 48 VDC logic power networks without hardware modification?A: The voltage operational band is selected via onboard configuration jumpers. The physical links must be placed in the correct 24 VDC (22-30 VDC) or 48 VDC (43-60 VDC) position before energizing the system.

Field Installation Guidelines

  • DIN-Rail Attachment: Securely latch the housing onto an EN 50022 35 mm DIN-rail using top and bottom retention clamps. Ensure minimum 50 mm clearance above and below the unit for natural convection cooling.
  • Grounding & Shielding: Connect the system protective earth terminal directly to the enclosure grounding bar using low-impedance copper strap (minimum 4 mm sq cross-section). Keep field wiring shields continuous through designated terminal blocks.
  • Power Connection Integrity: Torque all input screw terminals to manufacturer specifications (typically 0.5 to 0.6 Nm) to avoid contact heating under full 23 A load conditions.
  • Fusing Precautions: Verify replacement fuses strictly comply with IEC 60269-1 standards at the designated 3.15 A current rating to preserve SIL3 trip characteristics.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.