Skip to content
ICS Triplex T8451 TMR 24Vdc Digital Output Module

ICS Triplex T8451 TMR 24Vdc Digital Output Module

  • 1000 In stock
  • Manufacturer: Allen-Bradley

  • Product No.: T8451

  • Condition: In stock

  • Product Type: TMR 24Vdc Digital Output Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 1130g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":41499332640858,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"T8451","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ICS Triplex T8451 TMR 24Vdc Digital Output Module","public_title":null,"options":["Default Title"],"price":19600,"weight":1130,"compare_at_price":46300,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

ICS Triplex T8451 TMR 24Vdc Digital Output Module

Configured for safety-critical digital load switching in Trusted Safety Instrument System platforms, the ICS Triplex T8451 (T8451 TMR Digital Output Module) provides direct physical/electrical execution. Operating on a 24 VDC nominal field and system architecture, the assembly drives up to 40 individual output channels structured across five galvanically isolated power groups. Built-in triplicated control paths execute continuous hardware vote checks to maintain functional safety compliance while eliminating single-point vulnerabilities in mission-critical process loops.

Hardware Specifications

Parameter Specification
Model T8451
Brand ICS Triplex
Origin United Kingdom
Weight 1.13 kg
Dimensions 30 cm x 3 cm x 24.1 cm
Operating Temp -5 deg C to 60 deg C
Power Consumption 24 W Field Supply (1 A per channel), 24 W System Supply (at 24 VDC)
System Supply Voltage Range 20 VDC to 32 VDC
Output Circuit Type Fault-tolerant, fully triplicated with optional line monitoring
Number of Outputs 40 channels (5 independent groups of 8 outputs)
Output Voltage Range 18 VDC to 32 VDC
Measurement Range 0 VDC to 32 VDC
Maximum Withstanding Voltage -1 VDC to 40 VDC
Output Current Rating 2 A per channel (8 A maximum per power group)
Field Common Isolation Sustained Working: +/-250 VDC, Maximum Withstanding: +/-2.5 kVDC
Turn-on / Turn-off Delay 0.5 ms
Sample Update Time 0.5 ms
Event Resolution 1 ms
Self-Test Interval 2 minutes

SIL3 Certification and TMR Architecture Execution

The ICS Triplex T8451 employs a Triple Modular Redundant (TMR) 2oo3 architecture designed for SIL3 certified safety applications. Internal hardware fault tolerance relies on three parallel processing lanes executing majority logic voting prior to output stage actuation. Comprehensive internal self-test diagnostics execute automatically every 2 minutes to detect dormant faults, while background galvanic isolation up to +/-2.5 kVDC prevents field-side voltage transients from compromising backplane logic processing. Fail-safe state execution guarantees deterministic de-energization upon critical fault detection.

Frequently Asked Questions

Q: What is the maximum switching delay and update performance of the module outputs?

A: Output turn-on and turn-off propagation delays are rated at 0.5 ms, matching the internal sample update time of 0.5 ms. Sequence of Events (SOE) resolution is maintained at 1 ms.

Q: How is field voltage isolation maintained across adjacent channel groups?

A: The module is split into 5 independent power groups of 8 channels each. Sustained field common working isolation is rated for +/-250 VDC, with maximum transient withstand rating up to +/-2.5 kVDC.

Q: What are the current loading limits for individual channels and power groups?

A: Each channel supports a maximum continuous current rating of 2 A. However, total aggregate current per 8-channel power group must not exceed 8 A max.

Field Installation Guidelines

  • Verify module chassis engagement along vertical backplane slots within designated Trusted chassis enclosures.
  • Ensure field wiring terminals adhere to correct polarity across the 18 VDC to 32 VDC external supply range before applying system power.
  • Maintain strict separation between field supply wiring and sensitive signal buses to limit electromagnetic interference.
  • Ensure external grounding cable continuity matches system earth specs to satisfy +/-2.5 kVDC surge withstand criteria.
  • Operate strictly within environmental limits of -5 deg C to 60 deg C and 5% to 95% RH (non-condensing).

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.