{"id":44036531552346,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"T8801","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ICS Triplex T8801 Digital Input Field Termination Assembly","public_title":null,"options":["Default Title"],"price":12300,"weight":1200,"compare_at_price":32000,"inventory_management":"shopify","barcode":null,"requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Configured for 24 VDC discrete signal termination in Trusted TMR systems, the ICS Triplex T8801 (T8801 Digital Input FTA) provides direct field wiring interface.

Hardware Specifications

Parameter Specification
Model T8801
Brand ICS Triplex
Product Type 40-Channel 24 VDC Digital Input Field Termination Assembly (FTA)
Origin Not specified in supplied data
Number of Channels 40 digital input channels
Operating Voltage 24 VDC nominal field loop supply
Power Distribution Dual 24 VDC feeds with diode commoning
Channel Protection 220 ohm current-limiting resistor per field loop
Compatible Module T8403 24 VDC TMR Digital Input Card
Signal Compatibility Dry contacts, wet contacts, non-incendive field switches
Mounting DIN-rail or rack-mounted inside Trusted system cabinet
Enclosure Rating IP20
Operating Temp 0 deg C to +60 deg C
Weight 1.2 kg
Dimensions 30.0 x 21.0 x 7.0 cm
Safety Architecture Trusted Triple Modular Redundant (TMR) system interface
Safety Application SIL 3 SIS integration
Hazardous Area Compatibility Non-incendive field loop circuits

TMR Digital Input Signal Termination

The T8801 routes discrete field signals toward the T8403 input module through dedicated termination circuitry.

Each channel incorporates a 220 ohm current-limiting resistor for field-loop signal conditioning and circuit protection.

Dual 24 VDC feeds use diode commoning, providing redundant power distribution to connected field input circuits.

The assembly supports dry contacts, wet contacts, and non-incendive field switches connected through discrete input loops.

The interface supports triple-redundant signal processing when paired with the specified T8403 TMR digital input card.

Frequently Asked Questions

Q: How many digital input channels does the T8801 provide?
A: The T8801 provides 40 discrete input channels for connection with compatible field switching devices.

Q: Which Trusted system module connects directly with the T8801?
A: The specified interface module is the T8403 24 VDC TMR Digital Input Card.

Q: What field-loop protection does each input channel provide?
A: Each field loop includes a 220 ohm current-limiting resistor for input circuit protection.

Field Installation Guidelines

Install the T8801 on the specified DIN rail or rack location inside the Trusted cabinet.

Verify cabinet clearances and mechanical retention before terminating field conductors at the assembly.

Route digital input wiring separately from high-voltage power conductors and high-current switching circuits.

Maintain consistent terminal identification between field devices, T8801 channels, and the associated T8403 input module.

Use shielded instrumentation cable where required by the installed system design and electromagnetic environment.

Terminate cable shields according to the project grounding specification, avoiding unintended multiple-point shield connections.

Verify both 24 VDC feeds before energization, including polarity, continuity, and diode-commoned supply arrangement.

Confirm field-loop voltage and signal state before connecting live conductors to the termination assembly.

For hazardous-area circuits, verify the installed wiring method against the applicable non-incendive system requirements.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products