{"id":44042915774554,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"T9851","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ICS Triplex T9851 Digital Output Termination Assembly","public_title":null,"options":["Default Title"],"price":12300,"weight":800,"compare_at_price":32000,"inventory_management":"shopify","barcode":null,"requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

The ICS Triplex T9851, also cataloged as the T9851 Digital Output Termination Assembly, provides the physical field-wiring interface between AADvance digital output modules and field actuators. It supports digital output termination for safety controller applications and interfaces with field devices such as valves, solenoids, and alarm relays.

Hardware Specifications

Parameter Specification
Model T9851
Brand ICS Triplex / Rockwell Automation
Series AADvance T9000
Module Type Digital Output Termination Assembly (TA)
System Compatibility AADvance T9000 Safety Controller
Architecture TMR and DMR configurations
Operating Voltage 18 to 32 VDC
Nominal Voltage 24 VDC
Channel Configuration Multi-channel digital output field wiring
Safety Integrity Level SIL 2 / SIL 3, IEC 61508
Mounting DIN rail or baseplate
Weight 0.8 kg
Dimensions 13 x 4 x 4.5 cm
Operating Temp -40 deg C to +70 deg C

AADvance Safety Termination and Redundancy

The T9851 provides the field termination point for digital output circuits associated with the AADvance safety controller. Its termination function separates cabinet-side controller wiring from field actuator connections and supports multi-channel digital output circuits.

The assembly is specified for AADvance TMR and DMR architectures. In TMR configurations, the termination interface forms part of a three-channel safety control arrangement. The supplied data specifies SIL 2 / SIL 3 application capability according to IEC 61508. Field wiring connections are provided through screw-terminal or spring-clamp interfaces according to the installed termination configuration.

Frequently Asked Questions

Q: What voltage range is specified for the T9851?

A: The supplied data specifies an operating range of 18 to 32 VDC, with 24 VDC as the nominal operating voltage.

Q: Is the T9851 compatible with redundant AADvance architectures?

A: Yes. The supplied data specifies compatibility with both TMR and DMR AADvance configurations.

Q: Can the T9851 be replaced during system maintenance?

A: The supplied data identifies hot-swappable support for maintenance and replacement. The applicable system maintenance procedure should be followed before removal or replacement.

Field Installation Guidelines

Install the T9851 on the specified DIN rail or baseplate within the AADvance controller cabinet. Verify that the mounting hardware provides mechanical retention before connecting field wiring.

Route digital output conductors separately from high-energy power wiring where practical to reduce electromagnetic coupling. Maintain appropriate separation between signal and power circuits according to the cabinet wiring standard.

Terminate field conductors using the applicable terminal interface and verify conductor identification against the system wiring documentation. Cable shields, where used, should be bonded according to the project grounding and EMC design.

Before energizing the circuit, verify polarity, terminal assignment, supply voltage, and actuator wiring continuity. For redundant safety architectures, confirm that all termination connections correspond to the designated controller channels.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products