ProSoft MVI56E-61850S IEC 61850 Server Communication Module

ProSoft MVI56E-61850S IEC 61850 Server Communication Module

  • 16 In stock
  • Manufacturer: AMPHENOL

  • Product No.: MVI56E-61850S

  • Condition: In stock

  • Product Type: IEC 61850 Server Communication Module

  • Payment:T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":43996927590490,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"MVI56E-61850S","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ProSoft MVI56E-61850S IEC 61850 Server Communication Module","public_title":null,"options":["Default Title"],"price":12300,"weight":500,"compare_at_price":32000,"inventory_management":"shopify","barcode":null,"requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

The ProSoft MVI56E-61850S, also cataloged as the MVI56E-61850S Communication Module, operates as a dedicated hardware component for bridging IEC 61850 protocol data with ControlLogix backplanes within Allen-Bradley ControlLogix PAC systems.

Hardware Specifications

Parameter Specification
Model MVI56E-61850S
Brand ProSoft Technology
Origin USA
Weight 0.5 kg
Operating Temp 0 to 60 deg C (32 to 140 deg F)
Power Consumption 4.5 W
Backplane Current Load 800 mA at 5.1 VDC; 3 mA at 24 VDC
Storage Temperature -40 to 85 deg C (-40 to 185 deg F)
Relative Humidity 5% to 95% (non-condensing)
Ethernet Ports 2 x 10/100 Base-T RJ45
Display 4-character alphanumeric LED
Protocol Support IEC 61850 MMS Server, GOOSE (Publish and Subscribe)
Simultaneous MMS Clients Up to 5 connections
Supported Data Types Boolean, Single/Double Precision Float, Integer, Structure

Protocol Conversion Latencies

The MVI56E-61850S maintains deterministic timing performance across the ControlLogix 1756 backplane by executing optimized protocol conversion latencies for real-time data transfer. Incoming IEC 61850 MMS data attributes and peer-to-peer GOOSE (Generic Object Oriented Substation Events) messages are processed within dedicated memory registers, minimizing cyclic scan-time impact on the primary controller. Dual Ethernet ports allow logical subnet isolation, ensuring low-latency packet prioritization during high-frequency GOOSE broadcast cycles across substation networks.

Frequently Asked Questions

Q: How many simultaneous MMS Client connections are supported by the MVI56E-61850S module?

A: The module supports up to 5 simultaneous MMS Client connections for data polling and SCADA integration.

Q: What are the backplane power requirements for installing this module into a ControlLogix rack?

A: The module draws 800 mA at 5.1 VDC and 3 mA at 24 VDC from the 1756 backplane, resulting in a total power dissipation of 4.5 W.

Q: Does the module support hot-swapping during active system operation?

A: Yes, as a standard ControlLogix module, it supports Removal and Insertion Under Power (RIUP) without disrupting parallel chassis operations or backplane communications.

Field Installation Guidelines

  1. Power down the 1756 ControlLogix chassis before physical insertion or ensure proper RIUP precautions are strictly followed.
  2. Align the module with the top and bottom chassis guides and slide it firmly into the target slot until the lever locks securely into place.
  3. Connect Category 5e or higher shielded twisted-pair (STP) Ethernet cables to the RJ45 ports. Ensure cable shields are grounded at the switch end to reduce electromagnetic interference.
  4. Verify that the chassis earth ground bus is connected to the primary protective earth (PE) using minimum 10 AWG copper wire.
  5. Apply power to the chassis and verify initialization sequences via the 4-character alphanumeric diagnostic LED display.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products