Skip to content
ProSoft MVI56E-MNET Modbus TCP ControlLogix Gateway Module

ProSoft MVI56E-MNET Modbus TCP ControlLogix Gateway Module

  • 1000 In stock
  • Manufacturer: Allen-Bradley

  • Product No.: MVI56E-MNET

  • Condition: In stock

  • Product Type: Modbus TCP ControlLogix Gateway Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 408g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":43290082410586,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"MVI56E-MNET","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"ProSoft MVI56E-MNET Modbus TCP ControlLogix Gateway Module","public_title":null,"options":["Default Title"],"price":18800,"weight":408,"compare_at_price":32000,"inventory_management":"shopify","barcode":"USA","requires_selling_plan":false,"selling_plan_allocations":[],"quantity_rule":{"min":1,"max":null,"increment":1}}

Description

Product Overview

The ProSoft MVI56E-MNET is an Ethernet-based communication interface developed for Allen-Bradley ControlLogix platforms, enabling direct connectivity to Modbus TCP/IP networks. It is engineered to allow PLC processors to exchange data with a wide variety of Modbus-compatible field devices such as controllers, drives, instrumentation systems, and remote I/O stations.

As part of ProSoft’s Enhanced E-Series architecture, this module focuses on higher throughput, expanded memory handling, and improved system diagnostics compared to earlier generation modules.

Communication Capabilities

Modbus TCP/IP Interface

  • Protocol Standard: Modbus TCP/IP over Ethernet

  • Operating Modes: Client (Master), Server (Slave), or simultaneous operation

  • Ethernet Interface: 10/100 Mbps auto-negotiation, full/half duplex

  • Connection Capacity:

    • Up to 30 client sessions

    • Up to 10 server sessions

  • Supported Function Codes:

    • Coil read/write

    • Holding register read/write

    • Input register access

    • Discrete input monitoring

  • Data Capacity: Supports up to 10,000 registers

  • Data Types: Integer, floating-point, and bit-level mapping

ControlLogix System Integration

  • Platform Compatibility: Allen-Bradley ControlLogix

  • Slot Requirement: Single standard ControlLogix slot

  • Backplane Communication: High-speed optimized data transfer architecture

  • Configuration Tool: ProSoft Configuration Builder (PCB)

  • Diagnostics Interface: Embedded web server for live monitoring

  • Status Indicators: Module health, Ethernet activity, application state, and backplane status

Electrical & Environmental Specifications

Parameter Specification
Backplane Current Load 800 mA @ 5 VDC
Auxiliary Supply 3 mA @ 24 VDC
Operating Temperature 0°C to 60°C
Extended Version -25°C to 70°C (XT variant)
Storage Temperature -40°C to 85°C
Humidity 5–95% non-condensing
Vibration 5 g (10–150 Hz)
Shock 30 g operational / 50 g non-operational
Electrical Isolation 1500 V (Ethernet to backplane)

Engineering Features

  • High-throughput Modbus TCP/IP processing engine

  • Dual-mode client/server communication support

  • Optimized backplane bandwidth utilization

  • Large-scale data block handling up to 10,000 registers

  • Built-in web diagnostics for troubleshooting and monitoring

  • Support for redundant Ethernet network architectures

  • Stable operation under continuous industrial load conditions

Typical Applications

  • SCADA and distributed control systems

  • Oil & gas production and pipeline monitoring

  • Power generation control and auxiliary systems

  • Water and wastewater treatment facilities

  • Chemical and petrochemical processing plants

  • Manufacturing automation networks

FAQ

Q1: Can this module operate in both client and server modes simultaneously?
Yes, it supports concurrent Modbus TCP client and server operations.

Q2: How many devices can it communicate with?
It supports up to 30 client and 10 server connections simultaneously.

Q3: Is web-based diagnostics available?
Yes, it includes an embedded web server for real-time diagnostics and statistics.

Q4: Does it support large data handling?
Yes, it can manage up to 10,000 Modbus registers with multiple data formats.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured