Description
ProSoft Technology PLX82-EIP-PNC EtherNet/IP to PROFINET Controller Gateway
Configured for bi-directional protocol conversion between EtherNet/IP controllers and PROFINET RT devices, the ProSoft Technology PLX82-EIP-PNC (PLX82-EIP-PNC gateway) provides direct network-level data exchange between the two industrial Ethernet protocols.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | PLX82-EIP-PNC |
| Brand | ProSoft Technology |
| Origin | Not specified in supplied data |
| Product Type | EtherNet/IP to PROFINET Controller Gateways |
| Weight | 3.10 lbs |
| Dimensions | 14.01 cm x 5.24 cm x 11.09 cm |
| Operating Temp | 0 deg C to 50 deg C |
| Power Consumption | 400 mA at 24 VDC nominal; 610 mA maximum |
| Power Supply | 24 VDC nominal; 10 to 36 VDC allowed |
| Ethernet Ports | 2 x 10/100 Mbps RJ45 |
| Electrical Isolation | 1500 Vrms at 50 to 60 Hz for 60 seconds |
| EtherNet/IP Connections | Class 1 I/O: up to 20; Class 3 Server: 5; Class 3 Client: 2 |
| EtherNet/IP I/O Data | 248 bytes input / 248 bytes output per connection |
| Minimum RPI | 2 ms for 1 connection; 8 ms for 8 connections |
| PROFINET Role | Class 1 RTC / Class 1 RTA IO Controller |
| Maximum PROFINET Devices | Up to 36 devices |
| PROFINET I/O Data | Up to 1440 bytes in/out per device |
| Total PROFINET I/O Data | 3840 bytes IN / 3840 bytes OUT |
| Relative Humidity | 5% to 95% RH, non-condensing |
| Storage Temperature | -10 deg C to 70 deg C |
| Mounting | Standard 35 mm DIN rail |
Protocol Conversion and Network Isolation
The PLX82-EIP-PNC operates as an EtherNet/IP adapter and a PROFINET IO Controller. It supports bi-directional exchange between EtherNet/IP PLC systems and PROFINET RT field devices.
Two isolated Ethernet ports separate EtherNet/IP and PROFINET network traffic onto independent physical interfaces and subnets. The specified electrical isolation rating is 1500 Vrms at 50 to 60 Hz for 60 seconds.
Embedded Add-On Profiles and EDS files support configuration within Studio 5000 and RSLogix 5000 environments. An onboard SD card provides configuration storage for replacement and recovery procedures.
The gateway supports up to 36 PROFINET devices, with a total PROFINET data capacity of 3840 bytes input and 3840 bytes output.
Protocol conversion latency depends on the configured EtherNet/IP connection count and requested packet interval. The supplied specifications state a minimum RPI of 2 ms for one connection and 8 ms for eight connections.
Frequently Asked Questions
Q: Can the PLX82-EIP-PNC directly control PROFINET RT devices from an EtherNet/IP PLC?
A: Yes. The gateway functions as a PROFINET Class 1 IO Controller while communicating with the EtherNet/IP PLC as an EtherNet/IP adapter.
Q: How many PROFINET devices can the gateway manage?
A: The supplied specification permits up to 36 PROFINET devices, with up to 1440 bytes of input and output data per device.
Q: What mounting arrangement is specified for field installation?
A: The unit is specified for standard 35 mm DIN-rail mounting. Maintain adequate wiring clearance around both Ethernet interfaces and the power terminals.
Field Installation Guidelines
Install the gateway on a mechanically secure 35 mm DIN rail within the specified operating temperature and humidity limits.
Connect the 24 VDC supply within the stated 10 to 36 VDC input range, observing correct polarity and protective grounding requirements.
Route EtherNet/IP and PROFINET cables separately where practical, particularly from high-current switching conductors, motor cables, and other high-noise sources.
Use shielded industrial Ethernet cabling where the network design requires electromagnetic noise control. Terminate cable shields according to the plant grounding scheme and avoid uncontrolled multiple-point shield connections.
Assign the two Ethernet interfaces to their intended network segments. Verify IP addressing, subnet configuration, EtherNet/IP connection parameters, and PROFINET device configuration before placing the gateway into service.
Use the SD card for configuration backup and controlled replacement procedures. Confirm that stored configuration data matches the installed hardware and network topology before recovery.
Do not exceed the specified EtherNet/IP connection limits, PROFINET device count, or I/O data capacities during configuration.
Features
We welcome bulk orders and have a minimum order quantity of just one unit.
Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.
For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.
We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.
We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.
Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.