Описание
Product Description
The ABB REJ603BBB10NN3XC is a self-powered feeder protection relay engineered for medium-voltage secondary distribution networks. Unlike traditional relays, it derives operating power directly from the current transformer (CT) input, eliminating the need for an auxiliary power source. This design makes it ideal for applications where external power is limited, such as ring main units (RMUs), compact substations, and distribution automation projects.
Technical Specifications
| Attribute | Details |
|---|---|
| Manufacturer | ABB |
| Series | Relion® 600 |
| Model Number | REJ603BBB10NN3XC |
| Product Type | Self-Powered Feeder Protection Relay |
| Protection Functions | Phase overcurrent, Earth fault, Undervoltage/Overvoltage |
| Rated Frequency | 50 / 60 Hz |
| Rated Current | 1 A / 5 A (selectable) |
| Power Supply | Self-powered via CT input |
| Startup Power Requirement | ~2.5 VA at rated current |
| Trip Output | 1 NO (Normally Open) |
| Binary I/O | 1 Digital Input / 1 Digital Output (configurable) |
| Fault Recording | Up to 100 fault events stored |
| User Interface | LED indicators, DIP switch configuration |
| Communication | None by default; optional serial interface available |
| Configuration | Manual (DIP switches) or optional software |
| Enclosure Material | Flame-retardant plastic |
| Protection Class | IP54 front, IP20 rear |
| Dimensions (HxWxD) | 160 × 96 × 150 mm |
| Weight | 0.9 kg |
Key Features
-
Self-powered operation ensures deployment where auxiliary supply is unavailable.
-
Compact design fits RMUs, compact substations, and distribution cabinets.
-
Provides reliable protection against overcurrent, earth faults, and voltage irregularities.
-
Records up to 100 events for diagnostic analysis.
-
Simple configuration through DIP switches or optional software.
-
Durable construction with IP54-rated front for harsh environments.
Applications
-
Secondary distribution networks in medium-voltage systems
-
Ring Main Units (RMUs)
-
Compact Substations
-
Distribution automation projects with limited auxiliary power
FAQ
Q: Can the REJ603BBB10NN3XC be installed without any auxiliary power supply?
A: Yes. The relay is self-powered from the CT input and does not require an external voltage source.
Q: How many fault records can it store?
A: The relay stores up to 100 fault events for diagnostics and analysis.
Q: Is remote communication supported?
A: Standard units do not include communication, but optional serial interfaces are available upon request.
Q: How is the relay configured?
A: Configuration is performed using DIP switches or optional ABB configuration software.
Особенности
Мы приветствуем оптовые заказы и минимальное количество заказа всего одна единица.
По запросу мы можем предоставить всю необходимую документацию, включая сертификаты происхождения/соответствия и другие требуемые экспортные документы.
Для товаров в наличии мы стремимся доставить в течение 1-3 дней после подтверждения оплаты. Товары с указанными сроками поставки будут доставлены согласно заявленному графику.
Мы принимаем 100% оплату T/T (телеграфным переводом) до отправки. Для товаров с длительным сроком изготовления требуется предоплата в размере 30%, оставшиеся 70% оплачиваются перед отправкой. Для переводов в юанях (RMB) свяжитесь с нами, если у вас есть агент в Китае.
Мы предлагаем стандартную годовую гарантию на все новые и оригинальные товары. Если вам нужна расширенная гарантия, пожалуйста, свяжитесь с нами для получения информации о дополнительной стоимости.
Ваше удовлетворение важно для нас. Если вам нужно вернуть товар, это должно быть сделано в течение 30 дней с даты заказа. Продукт должен быть неиспользованным, нераспечатанным и в оригинальной упаковке со всеми включёнными аксессуарами. Возврат средств осуществляется в течение 5-7 рабочих дней после получения возвращённого товара. Обратите внимание, что стоимость доставки и сопутствующие расходы не подлежат возврату.