The KL3101X1-BA1 is an intrinsically safe (I.S.) analog input CHARM module from Emerson, engineered for DeltaV systems. It allows safe acquisition of 4–20 mA signals from HART-enabled field devices in hazardous environments, providing both measurement and diagnostic capabilities in a compact CHARM form factor.
This module is designed for installations in Zone 2 / Class I Division 2 areas, combining intrinsic safety, robust environmental tolerance, and compliance with ATEX, IECEx, FM, and UKEX standards. Its low-power CHARM bus interface and reliable 24 VDC field circuit support stable operation under demanding conditions.
Core Technical Specifications
-
Model: KL3101X1-BA1
-
Module Type: Intrinsically Safe Analog Input (I.S.) CHARM
-
Signal Type: 4–20 mA analog input with HART communication
-
Safety Classification: Intrinsically Safe (I.S.)
-
CHARM Bus Power: +6.3 VDC, 0 A nominal
-
Field Circuit Power: +24 VDC at 60 mA
-
Terminal Block Key: A1
-
Operating Temperature: –40 °C to +70 °C
-
Relative Humidity: 5–95%, non-condensing
-
Shock Resistance: 10 g, half-sine, 11 ms
-
Vibration: 2–13.2 Hz: 1 mm peak-to-peak; 13.2–150 Hz: 0.7 g
-
Airborne Contaminants Rating: ISA-S71.04 Class G3
-
Weight: 0.14 lbs
Safety & Compliance
-
Hazardous Atmosphere Ratings:
-
II 3(1) G Ex ec [ia Ga] IIC Gc
-
II 3G (1D) Ex ec [ia IIIC Da] IIC Gc
-
Class I, Division 2, Groups A–D
-
Zone 2 AEx ec [ia Ga / IIIC Da]
-
Certifications: ATEX, IECEx, FM, UKEX
-
Installation Note: Must not be inserted or removed while energized unless the area is confirmed non-hazardous
Functional Advantages
-
Intrinsically safe design suitable for hazardous locations
-
HART support enables device diagnostics and configuration without extra wiring
-
Wide environmental tolerance for extreme temperatures and airborne contaminants
-
Compact CHARM format integrates seamlessly into DeltaV I/O systems
-
Maintenance-free operation; no calibration required
Applications
-
Oil and gas process control panels
-
Chemical and petrochemical plant field monitoring
-
Remote hazardous area I/O installations
-
Integration with DeltaV distributed control systems
FAQ
Q: Can this module operate in Zone 2 / Class I Div. 2 hazardous areas?
A: Yes, the KL3101X1-BA1 is certified intrinsically safe for Zone 2 / Class I Division 2 locations.
Q: Does it require periodic calibration?
A: No, the module is maintenance-free and factory-calibrated.
Q: What HART capabilities does it support?
A: Full pass-through communication for diagnostics and configuration of HART-enabled transmitters.
Özellikler
Toplu siparişleri memnuniyetle karşılıyoruz ve minimum sipariş miktarımız sadece bir birimdir.
Talep üzerine, Menşe/ Uygunluk Sertifikaları ve diğer gerekli ihracat belgeleri dahil olmak üzere tüm gerekli belgeleri sağlayabiliriz.
Stokta bulunan ürünler için, ödeme onayından sonra 1-3 gün içinde teslim etmeyi hedefliyoruz. Belirtilen teslim sürelerine sahip ürünler, belirtilen programa göre teslim edilecektir.
Gönderimden önce %100 T/T (Telgraf Transferi) ödemesini kabul ediyoruz. Teslim süresi olan ürünler için %30 depozito önceden alınır, kalan %70 ise gönderimden önce ödenir. RMB transferleri için, Çin'de bir temsilciniz varsa lütfen bizimle iletişime geçin.
Tüm yeni ve orijinal ürünlerde standart bir yıllık garanti sunuyoruz. Uzatılmış garanti talep ediyorsanız, lütfen ek maliyet detayları için bizimle iletişime geçin.
Memnuniyetiniz bizim için önemlidir. Bir ürünü iade etmeniz gerekiyorsa, bu sipariş tarihinden itibaren 30 gün içinde yapılmalıdır. Ürün kullanılmamış, açılmamış ve tüm aksesuarlarıyla birlikte orijinal ambalajında olmalıdır. İadeler, iade edilen ürünü aldıktan sonra 5-7 iş günü içinde işlenir. Lütfen nakliye ve ilgili ücretlerin iade edilmediğini unutmayın.