Açıklama
Product Description
The KL3106X1-BA1 is an intrinsically safe (I.S.) analog input CHARM module from Emerson, specifically designed for thermocouple signal acquisition in DeltaV systems. It allows precise and reliable temperature measurement in hazardous areas while maintaining compliance with global safety standards.
This compact CHARM module integrates directly into DeltaV racks, providing single-channel thermocouple input with low CHARM bus power consumption. The terminal block key position BA1 ensures correct wiring and installation, while the rugged design withstands vibration, shock, and airborne contaminants. No calibration is required, and the module has no user-serviceable parts, making it maintenance-free.
Technical Specifications
-
Model: KL3106X1-BA1
-
Module Type: Intrinsically Safe Analog Input (AI) CHARM
-
Signal Type: Thermocouple input (supports multiple types)
-
Safety Type: Intrinsically Safe (I.S.)
-
CHARM Bus Power: +6.3 VDC at minimal current
-
Field Circuit Power: +24 VDC, ~23 mA
-
Channels: Single-channel
-
Terminal Block Key Position: BA1
-
Operating Temperature: –40 °C to +70 °C
-
Humidity: 5–95% RH, non-condensing
-
Shock Resistance: 10 g, half-sine wave, 11 ms
-
Vibration: 2–13.2 Hz: 1 mm peak-to-peak; 13.2–150 Hz: 0.7 g
-
Airborne Contaminants: ISA-S71.04-1985 Class G3
Safety & Compliance
-
Hazardous Atmosphere Ratings:
-
II 3(1) G Ex ec [ia Ga] IIC Gc
-
II 3G (1D) Ex ec [ia IIIC Da] IIC Gc
-
Class I, Division 2, Groups A–D
-
Zone 2 AEx ec [ia Ga/IIIC Da] IIC Gc
-
Certifications: ATEX, IECEx, FM, UKEX
-
Installation Note: Do not insert or remove while energized unless area is confirmed non-hazardous
Key Highlights
-
Single-channel thermocouple input for accurate temperature measurement
-
Intrinsically safe design suitable for hazardous environments
-
Compact CHARM form factor for seamless DeltaV system integration
-
Wide environmental tolerance: –40 °C to +70 °C, Class G3 airborne contaminants
-
Keyed terminal block BA1 ensures proper connection and installation
Applications
-
Hazardous area temperature monitoring using thermocouples
-
DeltaV systems requiring single-channel intrinsically safe analog input
-
Process plants in oil, gas, chemical, or other Zone 2 / Class I Div. 2 environments
FAQ
Q: Which thermocouple types are supported by KL3106X1-BA1?
A: The module supports standard thermocouple types (J, K, T, E, R, S, B, N) depending on configuration.
Q: Can it be used in Class I Division 2 areas?
A: Yes, it is certified for Zone 2 / Class I Div. 2 hazardous areas.
Q: Is calibration required for operation?
A: No, the module is factory-calibrated and requires no user maintenance.
Özellikler
Toplu siparişleri memnuniyetle karşılıyoruz ve minimum sipariş miktarımız sadece bir birimdir.
Talep üzerine, Menşe/ Uygunluk Sertifikaları ve diğer gerekli ihracat belgeleri dahil olmak üzere tüm gerekli belgeleri sağlayabiliriz.
Stokta bulunan ürünler için, ödeme onayından sonra 1-3 gün içinde teslim etmeyi hedefliyoruz. Belirtilen teslim sürelerine sahip ürünler, belirtilen programa göre teslim edilecektir.
Gönderimden önce %100 T/T (Telgraf Transferi) ödemesini kabul ediyoruz. Teslim süresi olan ürünler için %30 depozito önceden alınır, kalan %70 ise gönderimden önce ödenir. RMB transferleri için, Çin'de bir temsilciniz varsa lütfen bizimle iletişime geçin.
Tüm yeni ve orijinal ürünlerde standart bir yıllık garanti sunuyoruz. Uzatılmış garanti talep ediyorsanız, lütfen ek maliyet detayları için bizimle iletişime geçin.
Memnuniyetiniz bizim için önemlidir. Bir ürünü iade etmeniz gerekiyorsa, bu sipariş tarihinden itibaren 30 gün içinde yapılmalıdır. Ürün kullanılmamış, açılmamış ve tüm aksesuarlarıyla birlikte orijinal ambalajında olmalıdır. İadeler, iade edilen ürünü aldıktan sonra 5-7 iş günü içinde işlenir. Lütfen nakliye ve ilgili ücretlerin iade edilmediğini unutmayın.