Description
Overview
The SPA-ZC 400 is designed to connect REF 541/3/5, REM 543/5, or RET 541/3/5 devices to the IEC 61850-8-1 Station bus. This device facilitates communication in modern substations by supporting the IEC 61850 standard, which is crucial for substation automation and the engineering process.
The SPA-ZC 400 supports GOOSE messaging for fast horizontal communication between Intelligent Electronic Devices (IEDs). This functionality is essential for the real-time transmission of interlocking and blocking information. In addition, the device offers Ethernet access for IEDs via SPA over TCP/IP and Modbus over TCP/IP.
Optionally, the SPA-ZC 400 also enables dual port communication for fibre-optic SPA and LON®, further enhancing communication flexibility. Detailed installation and programming instructions can be found in the Installation and Commissioning manual.
Technical Specifications
General Specifications
- Model: SPA-ZC 400
- Dimensions: 195 x 50 x 26 mm
- Weight: 130 g
Interfaces
-
IED Interface:
- D-type subminiature connector for IEC 61850 traffic
- D-type subminiature connector for dual port communication
-
IEC 61850 LAN Interface:
- RJ-45 (STP CAT5e) for galvanic connections
- MT-RJ and LC multimode glass fibre transceivers
-
LON/SPA Interface (Optional):
- ST multimode glass fibre transmitter/receiver pair
- Snap-in multimode plastic fibre transmitter/receiver pair
Fibre Optic Connections
- SPA-ZF Optical Glass Fibres (Multimode graded index, part no. 1MRS755371)
- Plastic-Core Fibre Optic Cables (Mounting instructions, part no. 1MRS752089-MUM)
Diagnostic LEDs
- Power: Indicates power status
- Diagnostic: Red (Error), Green (Normal)
-
LAN Diagnostic LEDs:
- LINK: Connection status
- TX: Transmission activity
- RX: Reception activity
- LON/SPA Diagnostic LED: RX (Reception activity)
EMC Immunity
-
Burst disturbance test:
- Common mode: 2.5 kV
- Differential mode: 1.0 kV
-
Electrostatic discharge:
- Contact discharge: 6 kV
- Air discharge: 8 kV
-
Radio frequency interference:
- Conducted, common mode: 10 V (rms), 150 kHz to 80 MHz
- Radiated, amplitude-modulated: 10 V/m (rms), 80 MHz to 2700 MHz
- Radiated, pulse-modulated: 10 V/m, 900 MHz
- Fast transient disturbance: 4 kV at all terminals
-
Surge immunity:
- Power supply: 4 kV line-to-earth, 2 kV line-to-line
- Power frequency magnetic field: 300 A/m continuous
Electromagnetic Emissions
- Conducted RF emission (Mains terminals): EN 55011, Class A
- Radiated RF emission: EN 55011, Class A
CE Compliance
The SPA-ZC 400 complies with the following directives:
- EMC Directive 2004/108/EC
- Low Voltage Directive 2006/95/EC
Features
Ми вітаємо оптові замовлення і маємо мінімальну кількість замовлення всього в одну одиницю.
За запитом ми можемо надати всю необхідну документацію, включаючи Сертифікати походження/відповідності та інші необхідні експортні документи.
Для товарів на складі ми прагнемо доставити протягом 1-3 днів після підтвердження оплати. Товари з вказаними термінами виконання будуть доставлені відповідно до зазначеного графіка.
Ми приймаємо 100% оплату T/T (телеграфним переказом) перед відправкою. Для товарів з термінами виготовлення потрібен аванс у розмірі 30%, решта 70% сплачується перед відправкою. Для переказів у RMB, будь ласка, зв'яжіться з нами, якщо у вас є агент у Китаї.
Ми пропонуємо стандартну однорічну гарантію на всі нові та оригінальні товари. Якщо вам потрібна розширена гарантія, будь ласка, зв'яжіться з нами для отримання додаткової інформації про вартість.
Ваша задоволеність важлива для нас. Якщо вам потрібно повернути товар, це має бути зроблено протягом 30 днів з дати замовлення. Продукт повинен бути не використаним, не відкритим і в оригінальній упаковці з усіма включеними аксесуарами. Повернення коштів обробляються протягом 5-7 робочих днів після отримання поверненого товару. Зверніть увагу, що вартість доставки та пов'язані з нею збори не підлягають поверненню.