Beschreibung
Product Description
The KC4011X1-BQ1 from Emerson is a 40-pin simplex discrete output (DO) mass terminal block designed for DeltaV systems. It provides a secure and organized interface for connecting multiple DO cards to field devices, ensuring reliable signal distribution in hazardous areas.
Engineered for Zone 2 / Class I Division 2 installations, this terminal block features LS1 keyed connections to prevent wiring errors. Its robust construction ensures operation under extreme temperatures, humidity, vibration, and shock conditions. The compact form factor simplifies installation while maintaining high reliability for process automation applications.
Technical Specifications
-
Model: KC4011X1-BQ1
-
Module Type: Simplex Discrete Output Mass Terminal Block
-
Channels: 40-pin connections for discrete outputs
-
Compatibility: Designed for Emerson DeltaV DO cards (S-series and SIS systems)
-
Nominal Voltage: 24 VDC
-
Field Circuit Power: 24 VDC at 100 mA per channel
-
Dimensions: 110 × 45 × 120 mm
-
Weight: 0.4 kg
-
Operating Temperature: –40 °C to +70 °C
-
Humidity: 5–95% RH, non-condensing
-
Shock Resistance: 10 g, half-sine wave, 11 ms
-
Vibration: 2–13.2 Hz: 1 mm peak-to-peak; 13.2–150 Hz: 0.7 g
-
Airborne Contaminants: ISA-S71.04-1985 Class G3
-
Terminal Block Key Position: B4
Safety & Compliance
-
Hazardous Atmosphere Ratings:
-
II 3G Ex ec IIC Gc
-
Class I, Division 2, Groups A–D
-
Zone 2 AEx/Ex ec IIC Gc
-
Certifications: ATEX, IECEx, FM, UKEX approvals for hazardous locations
-
Installation Note: Follow proper procedures for installation, removal, and operation in hazardous areas
Key Highlights
-
Provides mass termination for up to 40 discrete outputs, reducing wiring complexity
-
Certified for hazardous environments (Zone 2 / Class I Div. 2)
-
Rugged design withstands temperature extremes, vibration, and shock
-
Compact and lightweight for easy integration into DeltaV racks
-
Ensures consistent and reliable signal distribution for control and automation
Applications
-
Termination of multiple discrete output signals in DeltaV systems
-
Hazardous area installations for process control in oil, gas, and chemical plants
-
Field wiring organization and protection for DO cards
FAQ
Q: Can KC4011X1-BQ1 be used with SIS DeltaV cards?
A: Yes, it is compatible with both standard S-series and SIS DO cards.
Q: What is the maximum current per channel?
A: Each channel supports up to 100 mA at 24 VDC.
Q: Is this terminal block suitable for Zone 2 hazardous areas?
A: Yes, it meets ATEX, IECEx, FM, and UKEX standards for Zone 2 / Class I Div. 2 environments.
Zeig mehr
Wir begrüßen Großbestellungen und haben eine Mindestbestellmenge von nur einer Einheit.
Auf Anfrage können wir alle notwendigen Dokumente bereitstellen, einschließlich Ursprungs-/Konformitätszertifikate und andere erforderliche Exportdokumente.
Für vorrätige Artikel streben wir eine Lieferung innerhalb von 1-3 Tagen nach Zahlungseingang an. Artikel mit angegebenen Lieferzeiten werden gemäß dem angegebenen Zeitplan geliefert.
Wir akzeptieren 100% T/T (Telegraphische Überweisung) Zahlung vor dem Versand. Für Artikel mit Lieferzeiten ist eine Anzahlung von 30% im Voraus erforderlich, der verbleibende Rest von 70% ist vor dem Versand fällig. Für RMB-Überweisungen kontaktieren Sie uns bitte, wenn Sie einen Agenten in China haben.
Wir bieten eine standardmäßige einjährige Garantie auf alle neuen und originalen Artikel. Wenn Sie eine erweiterte Garantie benötigen, kontaktieren Sie uns bitte für weitere Kostendetails.
Ihre Zufriedenheit ist uns wichtig. Wenn Sie einen Artikel zurückgeben müssen, muss dies innerhalb von 30 Tagen nach dem Bestelldatum erfolgen. Das Produkt muss unbenutzt, ungeöffnet und in der Originalverpackung mit allen Zubehörteilen sein. Rückerstattungen werden innerhalb von 5-7 Werktagen nach Erhalt des zurückgesandten Artikels bearbeitet. Bitte beachten Sie, dass Versand- und damit verbundene Gebühren nicht erstattungsfähig sind.