Beschreibung
Product Description
The KL3103X1-BA1 is an intrinsically safe (I.S.) digital input CHARM module from Emerson, designed for DeltaV systems. It supports 24 VDC dry contact signals, allowing direct connection of field devices such as switches, pushbuttons, and contact closures. This module ensures safe and reliable monitoring in hazardous locations, integrating seamlessly into the DeltaV CHARM architecture.
Engineered for Zone 2 / Class I Division 2 environments, the KL3103X1-BA1 combines intrinsic safety with robust environmental tolerance, including resistance to vibration, shock, and airborne contaminants. Its compact form factor and low-power CHARM bus interface facilitate easy installation and modular expansion.
Core Technical Specifications
-
Model: KL3103X1-BA1
-
Module Type: Intrinsically Safe Digital Input (DI) CHARM
-
Signal Type: 24 VDC dry contact
-
Safety Classification: Intrinsically Safe (I.S.)
-
CHARM Bus Power: +6.3 VDC, 32 mA
-
Field Circuit Power: +24 VDC, ~10 mA
-
Channels: Single-channel input
-
Terminal Block Key: 2C
-
Operating Temperature: –40 °C to +70 °C
-
Relative Humidity: 5–95% RH, non-condensing
-
Shock Resistance: 10 g, half-sine wave, 11 ms
-
Vibration: 2–13.2 Hz: 1 mm peak-to-peak; 13.2–150 Hz: 0.7 g
-
Airborne Contaminants Rating: ISA-S71.04 Class G3
-
Weight: 0.18 lbs
Safety & Compliance
-
Hazardous Area Ratings:
-
II 3G Ex nA [nL] IIC Gc
-
II 3G Ex ec [ic] IIC Gc
-
Class I, Division 2, Groups A–D
-
Zone 2 AEx/Ex ec [ic] IIC Gc
-
Certifications: ATEX, IECEx, FM, UKEX
-
Installation Note: Module must not be inserted or removed while energized unless the area is confirmed safe
Functional Advantages
-
Intrinsically safe design suitable for hazardous areas
-
Supports 24 VDC dry contact inputs for direct field device monitoring
-
Compact CHARM format allows easy integration and modular expansion
-
Robust diagnostics ensure reliable operation of connected field devices
-
Wide environmental tolerance for harsh industrial conditions
Applications
-
Monitoring switches and pushbuttons in oil and gas facilities
-
Remote hazardous area I/O panels
-
Chemical and petrochemical process control systems
-
DeltaV system integration for single-channel dry contact inputs
FAQ
Q: Is this module suitable for hazardous Zone 2 locations?
A: Yes, the KL3103X1-BA1 is certified intrinsically safe for Zone 2 / Class I Div. 2 hazardous areas.
Q: Can it monitor multiple devices?
A: This module provides a single-channel input; multiple modules can be installed for multi-device monitoring.
Q: Does it require calibration?
A: No calibration is required, and the module has no user-serviceable parts.
Zeig mehr
Wir begrüßen Großbestellungen und haben eine Mindestbestellmenge von nur einer Einheit.
Auf Anfrage können wir alle notwendigen Dokumente bereitstellen, einschließlich Ursprungs-/Konformitätszertifikate und andere erforderliche Exportdokumente.
Für vorrätige Artikel streben wir eine Lieferung innerhalb von 1-3 Tagen nach Zahlungseingang an. Artikel mit angegebenen Lieferzeiten werden gemäß dem angegebenen Zeitplan geliefert.
Wir akzeptieren 100% T/T (Telegraphische Überweisung) Zahlung vor dem Versand. Für Artikel mit Lieferzeiten ist eine Anzahlung von 30% im Voraus erforderlich, der verbleibende Rest von 70% ist vor dem Versand fällig. Für RMB-Überweisungen kontaktieren Sie uns bitte, wenn Sie einen Agenten in China haben.
Wir bieten eine standardmäßige einjährige Garantie auf alle neuen und originalen Artikel. Wenn Sie eine erweiterte Garantie benötigen, kontaktieren Sie uns bitte für weitere Kostendetails.
Ihre Zufriedenheit ist uns wichtig. Wenn Sie einen Artikel zurückgeben müssen, muss dies innerhalb von 30 Tagen nach dem Bestelldatum erfolgen. Das Produkt muss unbenutzt, ungeöffnet und in der Originalverpackung mit allen Zubehörteilen sein. Rückerstattungen werden innerhalb von 5-7 Werktagen nach Erhalt des zurückgesandten Artikels bearbeitet. Bitte beachten Sie, dass Versand- und damit verbundene Gebühren nicht erstattungsfähig sind.