Beschreibung
Overview
The IC670ALG620 module from GE Fanuc is a high-precision RTD input interface designed for Field Control systems. It supports four independent channels and is compatible with both 3-wire and 4-wire RTD sensors, including Platinum, Nickel, Nickel/Iron, and Copper types. The module converts resistance measurements into accurate temperature data for process monitoring, control applications, and industrial automation systems.
Key Features
-
Four fully isolated RTD input channels for flexible sensor integration
-
Supports 3-wire and 4-wire RTD configurations
-
Configurable measurement ranges: 0–500 Ω or 0–3000 Ω
-
Outputs in resistance (Ω), Celsius (°C), or Fahrenheit (°F) with tenths resolution
-
Built-in diagnostics for open-wire, short-circuit, overrange/underrange, and high/low alarms
-
No external loop power required, reducing installation complexity
-
Industrial-grade reliability for continuous operation
Technical Specifications
| Specification | Details |
|---|---|
| Model Number | IC670ALG620 |
| Input Channels | 4 independent RTD inputs (3-wire or 4-wire) |
| Supported RTD Types | Platinum, Nickel, Nickel/Iron, Copper |
| Resistance Ranges | 0–500 Ω, 0–3000 Ω (selectable) |
| Measurement Units | Ω, °C, °F (tenths resolution) |
| Scan Time | 210 ms (60 Hz), 230 ms (50 Hz) |
| Digital Resolution | 15-bit plus sign |
| Maximum Lead Resistance | 5 Ω per lead |
| Normal Mode Rejection | 60 dB at 50/60 Hz, 100% span |
| Temperature Sensitivity | ±0.004% of reading, ±1.5 mV/°C referred to input (0–60°C) |
| Fault Detection | Open RTD, short, underrange, overrange, high/low alarms |
| Power Requirements | Draws up to 190 mA from BIU supply, no loop power needed |
| Dimensions | 120 × 50 × 100 mm |
| Weight | 0.45 kg |
Applications
Ideal for process control systems, distributed control stations, and temperature monitoring in industrial environments where precise RTD measurements are required. It integrates seamlessly with GE Field Control systems for automated and reliable operation.
FAQ
Q: Can the module measure multiple RTD types simultaneously?
A: Yes, each channel can be individually configured for Platinum, Nickel, Nickel/Iron, or Copper RTDs.
Q: Is external power required for the RTDs?
A: No, the module does not require loop power; it draws power directly from the Bus Interface Unit.
Q: How is configuration performed?
A: The module is configured via a handheld device connected to the main Bus Interface Unit.
Zeig mehr
Wir begrüßen Großbestellungen und haben eine Mindestbestellmenge von nur einer Einheit.
Auf Anfrage können wir alle notwendigen Dokumente bereitstellen, einschließlich Ursprungs-/Konformitätszertifikate und andere erforderliche Exportdokumente.
Für vorrätige Artikel streben wir eine Lieferung innerhalb von 1-3 Tagen nach Zahlungseingang an. Artikel mit angegebenen Lieferzeiten werden gemäß dem angegebenen Zeitplan geliefert.
Wir akzeptieren 100% T/T (Telegraphische Überweisung) Zahlung vor dem Versand. Für Artikel mit Lieferzeiten ist eine Anzahlung von 30% im Voraus erforderlich, der verbleibende Rest von 70% ist vor dem Versand fällig. Für RMB-Überweisungen kontaktieren Sie uns bitte, wenn Sie einen Agenten in China haben.
Wir bieten eine standardmäßige einjährige Garantie auf alle neuen und originalen Artikel. Wenn Sie eine erweiterte Garantie benötigen, kontaktieren Sie uns bitte für weitere Kostendetails.
Ihre Zufriedenheit ist uns wichtig. Wenn Sie einen Artikel zurückgeben müssen, muss dies innerhalb von 30 Tagen nach dem Bestelldatum erfolgen. Das Produkt muss unbenutzt, ungeöffnet und in der Originalverpackung mit allen Zubehörteilen sein. Rückerstattungen werden innerhalb von 5-7 Werktagen nach Erhalt des zurückgesandten Artikels bearbeitet. Bitte beachten Sie, dass Versand- und damit verbundene Gebühren nicht erstattungsfähig sind.