Description
Overview
The EPRO CON021/915-080 is a high-precision eddy current signal converter designed for rotating machinery monitoring. It accurately measures shaft displacement, position, eccentricity, and speed/key signals. It is widely used in steam, gas, and hydro turbines, as well as compressors, pumps, and fans.
This model works with multiple eddy current probes, including PR6422, PR6423, PR6424, PR6425 (requires extended range converter), PR6426, and PR6453. It converts sensor signals into standardized analog outputs for integration with monitoring and protection systems. The CON021/915-080 is optimized for MMS 6000 and IMR 6000 rack systems and supports hot-swappable installation, ensuring continuous operation of critical rotating equipment.
Technical Specifications
| Parameter | Specification |
|---|---|
| Function | Eddy current signal converter for shaft displacement, position, eccentricity, and speed/key monitoring |
| Frequency Range | 0–20 kHz (-3 dB) |
| Rise Time | <15 μs for accurate dynamic measurement |
| Compatible Sensors | PR6422, PR6423, PR6424, PR6425 (extended range), PR6426, PR6453 |
| Supply Voltage | -23V to -32V (Output -4V to -20V) -21V to -32V (Output -2V to -18V) |
| Output Signal | Standardized analog output (depending on configuration) |
| Operating Temperature | -30°C to +100°C (-22°F to +212°F) |
| Shock & Vibration | 5g @ 60 Hz @ 25°C |
| Protection Class | IP20 |
| Housing Material | LMgSi 0.5 F22 Aluminum Alloy |
| Weight | 120 g |
| Mounting | Rack-based installation (MMS 6000 / IMR 6000 compatible) |
| Connections | Self-locking LEMO plug or screw terminal options |
| Integration | Hot-swappable for rack systems |
Applications
-
Steam, gas, and hydro turbine monitoring
-
Rotating machinery: compressors, pumps, and fans
-
Process control and protection systems
FAQ
Q1: Which sensors are compatible with CON021/915-080?
A1: Compatible with PR6422, PR6423, PR6424, PR6425 (extended range), PR6426, and PR6453.
Q2: Can this module be replaced while running?
A2: Yes, it supports hot-swappable installation in MMS 6000 and IMR 6000 racks.
Q3: What is the typical measurement range?
A3: Using PR6425 extended range, ±8.0 mm with ≤3% linearity error.
Q4: What is the operating temperature range?
A4: -30°C to +100°C, suitable for most industrial rotating machinery environments.
Fonctionnalités
Nous acceptons les commandes en gros et avons une quantité minimale de commande d'une seule unité.
Sur demande, nous pouvons fournir toute la documentation nécessaire, y compris les certificats d'origine/de conformité et autres documents d'exportation requis.
Pour les articles en stock, nous visons une livraison sous 1 à 3 jours après confirmation du paiement. Les articles avec des délais spécifiés seront livrés selon le calendrier indiqué.
Nous acceptons le paiement à 100 % par T/T (virement télégraphique) avant l'expédition. Pour les articles avec des délais de livraison, un acompte de 30 % est requis à l'avance, le solde de 70 % étant dû avant l'expédition. Pour les transferts en RMB, veuillez nous contacter si vous avez un agent en Chine.
Nous offrons une garantie standard d'un an sur tous les articles neufs et d'origine. Si vous souhaitez une garantie prolongée, veuillez nous contacter pour plus de détails sur les coûts supplémentaires.
Votre satisfaction est importante pour nous. Si vous devez retourner un article, cela doit être fait dans les 30 jours suivant la date de la commande. Le produit doit être inutilisé, non ouvert, et dans son emballage d'origine avec tous les accessoires inclus. Les remboursements sont traités dans les 5 à 7 jours ouvrables après réception de l'article retourné. Veuillez noter que les frais de livraison et les frais connexes ne sont pas remboursables.