Description
Overview
The IC670ALG620 module from GE Fanuc is a high-precision RTD input interface designed for Field Control systems. It supports four independent channels and is compatible with both 3-wire and 4-wire RTD sensors, including Platinum, Nickel, Nickel/Iron, and Copper types. The module converts resistance measurements into accurate temperature data for process monitoring, control applications, and industrial automation systems.
Key Features
-
Four fully isolated RTD input channels for flexible sensor integration
-
Supports 3-wire and 4-wire RTD configurations
-
Configurable measurement ranges: 0–500 Ω or 0–3000 Ω
-
Outputs in resistance (Ω), Celsius (°C), or Fahrenheit (°F) with tenths resolution
-
Built-in diagnostics for open-wire, short-circuit, overrange/underrange, and high/low alarms
-
No external loop power required, reducing installation complexity
-
Industrial-grade reliability for continuous operation
Technical Specifications
| Specification | Details |
|---|---|
| Model Number | IC670ALG620 |
| Input Channels | 4 independent RTD inputs (3-wire or 4-wire) |
| Supported RTD Types | Platinum, Nickel, Nickel/Iron, Copper |
| Resistance Ranges | 0–500 Ω, 0–3000 Ω (selectable) |
| Measurement Units | Ω, °C, °F (tenths resolution) |
| Scan Time | 210 ms (60 Hz), 230 ms (50 Hz) |
| Digital Resolution | 15-bit plus sign |
| Maximum Lead Resistance | 5 Ω per lead |
| Normal Mode Rejection | 60 dB at 50/60 Hz, 100% span |
| Temperature Sensitivity | ±0.004% of reading, ±1.5 mV/°C referred to input (0–60°C) |
| Fault Detection | Open RTD, short, underrange, overrange, high/low alarms |
| Power Requirements | Draws up to 190 mA from BIU supply, no loop power needed |
| Dimensions | 120 × 50 × 100 mm |
| Weight | 0.45 kg |
Applications
Ideal for process control systems, distributed control stations, and temperature monitoring in industrial environments where precise RTD measurements are required. It integrates seamlessly with GE Field Control systems for automated and reliable operation.
FAQ
Q: Can the module measure multiple RTD types simultaneously?
A: Yes, each channel can be individually configured for Platinum, Nickel, Nickel/Iron, or Copper RTDs.
Q: Is external power required for the RTDs?
A: No, the module does not require loop power; it draws power directly from the Bus Interface Unit.
Q: How is configuration performed?
A: The module is configured via a handheld device connected to the main Bus Interface Unit.
Fonctionnalités
Nous acceptons les commandes en gros et avons une quantité minimale de commande d'une seule unité.
Sur demande, nous pouvons fournir toute la documentation nécessaire, y compris les certificats d'origine/de conformité et autres documents d'exportation requis.
Pour les articles en stock, nous visons une livraison sous 1 à 3 jours après confirmation du paiement. Les articles avec des délais spécifiés seront livrés selon le calendrier indiqué.
Nous acceptons le paiement à 100 % par T/T (virement télégraphique) avant l'expédition. Pour les articles avec des délais de livraison, un acompte de 30 % est requis à l'avance, le solde de 70 % étant dû avant l'expédition. Pour les transferts en RMB, veuillez nous contacter si vous avez un agent en Chine.
Nous offrons une garantie standard d'un an sur tous les articles neufs et d'origine. Si vous souhaitez une garantie prolongée, veuillez nous contacter pour plus de détails sur les coûts supplémentaires.
Votre satisfaction est importante pour nous. Si vous devez retourner un article, cela doit être fait dans les 30 jours suivant la date de la commande. Le produit doit être inutilisé, non ouvert, et dans son emballage d'origine avec tous les accessoires inclus. Les remboursements sont traités dans les 5 à 7 jours ouvrables après réception de l'article retourné. Veuillez noter que les frais de livraison et les frais connexes ne sont pas remboursables.